Laserfiche WebLink
STP/Piping Sump Containment <br /> Tank # Assigned T=1 87 STP T-2 91 STP <br /> Test Method Used Hydrostatic Hydrostatic Hydrostatic Hydrostatic Hydrostatic Hydrostatic <br /> Test Equipment Mfr. /Model Incon TS -STS Sump Tester w/ + or - 0 .002 " <br /> Test Start Time 10 : 58am 11 : 52am <br /> Initial Reading 4. 2006 " 6 . 8401 " <br /> Test End Time 11 : 13am 12 : 07pm <br /> Final Reading 4. 2010 " 6 .8408 " <br /> Change in Readings + 0 .0004" +0 . 0007 " <br /> Pass/Fail Threshold/Criteria + or - 0 . 002 " + or - 0 . 002" + or - 0 . 002" + or - 0 . 002" + or - 0 . 002" + or - 0 . 002 " <br /> Result Pass Pass <br /> Under- Dispenser Containment ' <br /> UDC # #1 -2 #34 #5-6 #7 -8 #9 -10 #11 =12 <br /> Test Method Used Hydrostatic Hydrostatic Hydrostatic Hydrostatic Hydrostatic Hydrostatic <br /> Test Equipment Mfr. /Model Incon TS -STS Sump Tester w/ + or - 0 . 002 " <br /> Test Start Time 9 : 20am 9 : 40am 9 : 20am 9 : 20am 11 : 52am 10 : 58am <br /> Initial Reading 3 . 1960 " 7. 3967 " 6 .4478 " 2 .3091 7 . 6853 " 3 . 2526 " " <br /> Test End Time 9 : 35am 9 : 55am 9 : 35am 9 : 35am 12 : 07pm 11 : 13am <br /> Final Reading <br /> 3 . 1963 " 7 . 3950 " 6 .4469 " 2 . 3090 " 7 .6869 " 3 .2538 " <br /> Change in Readings + 0 . 0003 " -0 . 0017 " -0 . 0009 " -0 .0001 " + 0 . 0016" + 0 . 0012 " <br /> Pass/Fail Threshold /Criteria + or - 0 . 002" + or - 0 . 002 " + or - 0 . 002" + or - 0 . 002" + or - 0 . 002 " + or - 0 . 002" <br /> Result Pass Pass Pass Pass Pass Pass <br /> Fill Riser Containment <br /> Tank # Assigned <br /> Test Method Used Hydrostatic Hydrostatic Hydrostatic Hydrostatic Hydrostatic Hydrostatic <br /> Test Equipment Mfr. /Model Incon TS-STS Sump Tester w/ + or - 0 . 002" <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Readings <br /> Pass/Fail Threshold/Criteria + or - 0 . 002 " + or - 0 . 002" + or - 0 . 002" + or - 0 . 002 " + or - 0 . 002" + or - 0 . 002" <br /> Result <br /> Was an UMPA inspector present during testing ? Not Present <br /> Inspector Name : Date : <br /> I certify under penalty of law that the information provided here and in supporting documents is true , accurate and complete . <br /> Tester Name : Tester Signature: ��_ Date : <br /> 1 111125/19 <br /> i <br /> CERS = California Environmental Reporting System , ID = Identification, UST = Underground storage tank, ICC = International Code Council , <br /> NA = Not applicable, UDC = Under-dispenser containment <br /> i <br />