Laserfiche WebLink
Hazardous Waste Tank System October <br /> Final Assessment per CCR Title 22 <br /> ' Premier Hyundai of Tracy,3480 Naglee Dr. Tracy, CA 95304 2014 <br /> Seismic Calculation <br /> Seismic Calculation -Waste Oil Tank <br /> Rectangular, Vertical Closed Top, Flat Bottom, Double Walled <br /> Material of Construction: steel <br /> Shell Height, in 41.00 <br /> Shell Length, in 73.00 <br /> Working Volume, gal 432.00 <br /> S.G. of contents 0.95 <br /> Tank Wall Thickness, in 0.12 <br /> Total Wei ht of Tank and Contents, lbs 4337.00 <br /> Overturning Moment Arm, in 20.00 <br /> Resisting Moment Arm, in 23.00 <br /> Sds 0.89 <br /> Importance Factor 1.00 <br /> Fp, ASCE 7-10, 15.4-2 1157.98 <br /> E <br /> Overturning Moment inlbf 23159.58 <br /> Resisting Moment, inlbf 99751.00 <br /> Overturning Safety Factor- No Tension 4.31 <br /> Shear Strength of Anchor. Lbs 3432.00 <br /> # of Anchors 2.00 <br /> Factor of Safety for Shear 5.93 <br /> i <br /> Seismic/Anchoring findings: The tank as del"ed and operated and the <br /> containment area in which it is located are ade itely anchored and are <br /> seismically sound. Initials: <br /> Strandberg Associates 1(866) 388-0404 rwaterguy6a)rwaterguy.com 12 <br /> i <br />