Laserfiche WebLink
Hazardous Waste Tank System October <br /> Title 22 Assessment per CCR Title 22 <br /> Premier Dodge of Tracy, 3460 Naglee Drive, Tracy, CA 95304 20 14 <br /> Foundation Assessment <br /> Foundation Analysis, Used Oil Tank <br /> Soil Type: Clay Sandy, Allowable Pressure, psf 1500.00 <br /> area of foundation, ft2 17.24 <br /> depth of concrete, in 6.00 <br /> weight of concrete, lbs 1290.64 <br /> weight of tank and contents, lbs 2101.00 <br /> total weight on soil, lbs 3391.64 <br /> pressure on soil, psf 196.78 <br /> Safety Factor 7.62 <br /> Soil is Okay for Foundation <br /> Concrete Analysis <br /> fc', psi 2500.00 <br /> br 0.70 <br /> a 1.00 <br /> loaded area, in2 288.00 <br /> Foundation Bearing Capacity, Fb, lbs 214200.00 <br /> Combined weight of tank and contents, lbs 2101.00 <br /> Safety Factor 10195 <br /> — Foundation is Okay for tank. <br /> Integrity testing findi g : Based on the above noted integrity test and the <br /> results obtained from a test, the tank has sufficient integrity for its intended <br /> use. Initials: <br /> Strandberg Associates 1(866) 388-0404 ohn strandber associates.com 13 <br />