Laserfiche WebLink
Mike Smith Engineering, Inc. <br /> Box 611, Lodi, CA 95241 <br /> (209) 334-2332 <br /> 7/12/2017 <br /> California Tank Lines,Inc. <br /> 3105 S. El Dorado St. <br /> Stockton,CA <br /> RE: Tank Assessment For <br /> 275 Gallon Waste Oil Tank <br /> I <br /> A preliminary tank assessment has been performed upon the waste oil tank and secondary <br /> containment at the above referenced facility. The inspection was necessary to identify <br /> and certify the secondary containment for this system. <br /> The waste oil tank is a steel tank,rectangular in shape with a stainless steel containment. <br /> This containment has welded seams, and at the time of inspection showed no signs of <br /> cracks or leaks. This system is monitored by visual inspection on a daily basis. <br /> The tank has steel angle brackets bolted to the concrete slab to hold the tank in place <br /> during a seismic event. 'fire tank is a low profile tank. Therefore, overturning will not be <br /> a concern. <br /> This system appears to be adequate to protect against a hazardous waste spill. This letter <br /> is not intended to be a complete Title 22 tank assessment,!but a complete Title 22 <br /> assessment can be provided if necessary. <br /> Sincerely, <br /> ti. 7r. r <br /> 3- <br /> Michael W. Smith,P.E. <br /> R.C.E. 44590 <br /> Mire Smith Engineering, Inc. <br /> Page 1 of I <br />