Laserfiche WebLink
UNDERGROUND STORAGE TANK <br /> SECONDARY CONTAINMENT TESTING REPORT FORM (Page 2 of s) <br /> V. TANK SECONDARY CONTAINMENT INFORMATION <br /> Manufacturer Identify Tank ID from Section III for each Manufacturer <br /> Trusco A 0 B El I C 0 D ❑x <br /> A ❑ B ❑ I C ❑ I D <br /> Test Method Used: ❑Manufacturer Guidelines(Specify): <br /> ❑x Industry Code or Engineering Standard(Specify): PEI/RP 1200-17/Glass Steel Tank/-10 Hg. 1 hr. <br /> ❑Engineered Method (Specify): <br /> #of Attached Pages <br /> Attach the testing procedures and all documentation required to determine the results. 2 <br /> Tank Containment Testing Training and Certifications(List applicable certifications.) Expiration Date <br /> ICC Service Technician #5246802-UT 3/21/2021 <br /> Underground Storage Tank Tester License #90-1120 12/31/2022 <br /> VI. COMMENTS <br /> Provide any additional comments here. <br /> Tank A is a 12K Double Wall Glass Steel, designated for Super 91 Octane Gasoline. <br /> Tank B is a 12K Double Wall Glass Steel, designated for Regular 87 Octane Gasoline. <br /> Tank C & Tank D is a Double Compartment, Double Wall Glass Steel. Tank C is designated for 5K Regular 87 Octane <br /> Gasoline. Tank D is designated for 5K Diesel. <br /> Note: Tank C, and Tank D, have a common Tank Secondary Containment. <br /> VII. PRODUCT PIPING CONTAINMENT TESTING INFORMATION <br /> Manufacturer Identify Tank ID from Section III for each Manufacturer <br /> Smith FRP 1A ZB ZC 0 D [9 <br /> A ❑ I B ❑ I C ❑ I D ❑ <br /> Test Method Used: ❑Manufacturer Guidelines(Specify): <br /> ❑x Industry Code or Engineering Standard(Specify): PEI/RP 1200-17/Fiberglass Pipe/5 Psi 1 hr. <br /> ❑Engineered Method (Specify): <br /> #of Attached Pages <br /> Attach the testing procedures and all documentation required to determine the results. 2 <br /> Product Piping Containment Testing Training and Certifications(List applicable certifications.) Expiration Date <br /> ICC Service Technician #5246802-UT 3/21/2021 <br /> Under round Storage Tank Tester License #90-1120 12/31/2022 <br /> Interstitial Communication Verification Method Used: <br /> Release pressure at end of Product Piping Containment runs at UDC's where applicable. <br /> VIII. COMMENTS <br /> Provide any additional comments here. <br /> ID=Identification <br />