Laserfiche WebLink
A NJ O A Q U l N Environmental Health Department <br /> COUNTY— <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> ARCO AM/PM 3443 CHEROKEE RD, STOCKTON December 21, 2020 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 305 HSC 25290.1,25290.2, 25291 Failed to maintain secondary containment(e.g.failure of secondary containment <br /> testing). <br /> OBSERVATION: Brine was observed in the diesel fill sump indicating a leak in the secondary containment. <br /> REGULATION GUIDANCE: Secondary containment shall be impervious to the liquid and vapor of the substance <br /> contained and constructed to prevent structural weakening as a result of contact with any hazardous substances <br /> released from the primary containment. <br /> CORRECTIVE ACTION: Immediately contact a properly licensed,trained, and certified contractor to make repairs <br /> to the UST system under permit and inspection of the EHD. <br /> This is a Class II violation. <br /> 307 HSC 25290.1(c3), 25290.2(c3) Failure to keep water out of the secondary containment system (post-Jul 2003). <br /> OBSERVATION: Liquid was observed in the: <br /> •bottom of the diesel STP sump <br /> •bottom of the 91 STP sump <br /> REGULATION GUIDANCE: Secondary containment shall be constructed to prevent any liquid intrusion into the <br /> system by precipitation, infiltration, or surface runoff. <br /> CORRECTIVE ACTION: Immediately remove this liquid, make a hazardous waste determination per Title 22 <br /> hazardous waste regulations, and manage accordingly. Immediately contact a properly licensed, trained, and <br /> certified contractor to address the liquid intrusion into the 91 STP sump and diesel STP sump under permit and <br /> inspection of the EHD, if needed. <br /> This is a minor violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 1/20/2020. <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br /> of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br /> ($152). To schedule an appointment, please call (209)468-3420. <br /> Documents provided during inspection: Return to Compliance Certification, Corrective Action Statement, Blank <br /> Certificate of Financial Responsibility Form <br /> FA0024482 PR0542573 SCO01 12/21/2020 <br /> EHD 23-01 Rev.9/16/2020 Page 6 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />