Laserfiche WebLink
NOTES; <br /> O1 PROVIDE CONTROL CIRCUIT AND 3/4" CONDUIT TO <br /> CONDENSING UNIT ON ROOF. <br /> O2 EQUIPMENT DISCONNECT SWITCHES SHALL BE SUPPLIED AND <br /> PREWIRED FOR CONNECTION TO COOLER/FREEZER. ELECTRICAL <br /> CONTRACTOR SHALL MAKE FINAL CONNECTIONS. <br /> O3 ALL CONDUIT AND WIRE FOR ALL WALK-INS SHALL BE DONE <br /> OUTSIDE OF WALK-INS AND ALL PENETRATIONS SHALL BE <br /> SEALED PER THE NEC. <br /> O4 VERIFY ALL CONDUCTOR, CONDUIT, AND CIRCUIT BREAKER Architect of Record: <br /> SIZES OF THE COOLER/FREEZER COMPONENTS WITH FINAL Mariah B. Meyer <br /> SELECTION. REFER TO MANUFACTURERS RECOMMENDATIONS. <br /> 8131 Metcalf Avenue <br /> O E.C. SHALL PROVIDE (2)#12 AND (1)#12 GROUND IN 1/2" Suite 300 <br /> CONDUIT FOR 208V/1P ELECTRIC DEFROST CIRCUIT FROM Overland Park,KS 66204 <br /> CONDENSING UNIT. <br /> www.brrarch.com <br /> O6 WRAP CONDENSATE LINES WITH HEAT TAPE AND PROVIDE 120V <br /> CONNECTION. REFER TO HEAT TAPE MANUFACTURER. Tel:913-262-9095 <br /> Fax:913-262-9044 <br /> O7 J-BOX FOR CONNECTION TO DOOR HEAT TRACE. BOX LOCATION <br /> SHALL NOT INTERFERE WITH DOOR OPERATION. FINAL <br /> CONNECTION TO HEAT TRACE SHALL BE BY OTHERS. <br /> O8 RECEPTACLE RECESSED IN WALL FOR PAPER TOWEL <br /> DISPENSER. USE AN ARLINGTON INDUSTRIES RECESSED <br /> ELECTRICAL BOX (DVFRIW) OR EQUIVALENT TO MOUNTQ w <br /> STANDARD RECEPTACLE AND WALL PLATE CENTERED BEHIND 10 w z 1 o <br /> PAPER <br /> DIMENSIONS. <br /> DISPENSER. REF ARCHITECTURAL FOR ROUGH-IN � oLL p CO W 2 � w o X <br /> CCS T:Z of rY=UO o <br /> / O9 IN EACH SHOWER ROOM, MOUNT ONE FEED-THRU GFC I ¢ ~fn-P fY of O U D W <br /> RECEPTACLE AT 40" AFF. MOUNT ONE STANDARD RECEPTACLE 0 w w, ¢¢J oLL=w¢o w Oz m <br /> 2 AT 90" AFF CONNECTED TO PROTECTED LOAD SIDE OF GFC I I I a��o z a z p 5 o w Jj W a <br /> 1 RECEPTACLE. UPPER RECEPTACLE IS FOR WALL-MOUNTED Z co 0 D¢W¢-z Or-,0, <br /> 8 RECIRCULATION FAN. O �vzowo�Zwvu woo <br /> �w¢ cfWoowJwoo¢ <br /> ,GF �� �� 10 NEMA 15-50R MOUNTED AT 48" AFF FOR MULTI-COOK OVEN Q z 0 o on a 0 1 w W J z z LL LU <br /> o <br /> -- -- "K-82". <<a_ ��ww�¢wI< <br /> g -- 11 HAND DRYER CONNECTION. COORDINATE EXACT LOCATION AND fn w z��o w w o 0 0�o�� <br /> (2) NEMA 5-15\\ ELEVATION WITH ARCHITECTURAL DRAW I NGS PRIOR TO ROUGH- x o¢5M u [w M z x z D o <br /> 100A/3P 30A/3P ❑❑ I FOR WASHERS __ I J 22 2 2 2 22" I N (� o o n a o Of a¢ ¢¢ <br /> 45" 45" p <br /> 2 G '' ❑r I "LP:t 11 ,44 46 21 GF,4U' I 18 i 12 INSTALL DISCONNECT SWITCH FOR LAUNDRY EQUIPMENT ON <br /> 14 Q 47 36" 60� =- I � � I ® WALL. MAINTAIN WORKING CLEARANCE IN FRONT OF SWITCH <br /> 27' PER NEC 110.26. USE FLEXIBLE CONDUIT FROM SWITCH TO <br /> "LP5"© "LPt 36" 60" �p 3 "LPG' r_ 38 IG EQUIPMENT TERMINAL BLOCK. SEE WIRING DIAGRAMS ON CONSULTANT LOGO <br /> "Kp' KP" ®� _ i 20 2 ©2 54 11 X61 3 21 1 I EQUIPMENT. VERIFY MANUFACTURER'S ELECTRICAL <br /> 13 REQUIREMENTS PRIOR TO INSTALL. <br /> 8,10,12 1,15,1 I 3G' <br /> 75,7 21 J 11 i 13 CASH REGISTER & CPU SHALL HAVE QUAD RECEPTACLES ON <br /> (3) NEMA 14-30 3 9 DEDICATED CIRCUIT WITH ISOLATED GROUND. STUB UP <br /> --- I Q ® CONDUITS AT FUEL DESK IN THE DEAD CORNER OF MILLWORK <br /> FOR DRYERSI I LP5 CABINETS. LOCATE RECEPTACLE UNDER FIXED SHELF OF <br /> O C IL— I L- 1 I "27 MILLWORK. LOCATED AFTER MILLWORK CABINETS HAVE BEEN <br /> GF'440r "LPs" INSTALINS, FIELD VERIFY FINAL LOCATIONS PRIOR TO r m <br /> ROUGH3 LCP(E) LP3(E) <br /> 2 14 RECEPTACLE FOR FLY TRAP. TIE INTO LIGTHING CIRCUIT IN <br /> 11 ROOM. <br /> "LP5" <br /> �Q engineering consultants <br /> LP6 3 15 RELOCATE DIESEL EMERGENCY SHUT-OFF BUTTON. EXTEND <br /> + I CONDO I T AND W I R I NG AS NECESSARY. COORDINATE W I TH FUEL e50 E.Algonquin Road�Suite 250�Schaumburg,IL 60173 <br /> T:913.322.1400:www.rtmec.com <br /> i ❑ 11 4 O CONTRACTOR. <br /> i I / 111111111H 16 STUB OUT ALL CONDUITS TO CASHIER AREA IN "DEAD" <br /> FP(E) LP2(E) KP(� CORNER OF M I LLWORK. <br /> I GF,40" "5� � 15 "LPS" <br /> 2g 17 ALL 120V ELECTRICAL POWER TO CAR OR TRUCK CASHIER W <br /> F__ 2 AREAS MILLWORK SHALL ENTER FROM AN 8"x8" SURFACE O Z <br /> I �� I ` / © MOUNTED JUNCTION BOX AT 24" AFF. HOLD TIGHT TO Q O <br /> MDP(E) T1 61( 117" 17" EXTERIOR WALL. EXTEND CONDUITS AND FROM PREVIOUS — <br /> STUBS IN EXISTING DIESEL AREA. � Q <br /> +❑ 18 EXTEND ALL DATA, LINE AND LOW VOLTAGE WIRING AND d O <br /> CONDUIT AS NECESSARY FROM PREVIOUS STUB LOCATIONS IN W Ij <br /> GF,40" 3 I I 19 EXISTING DIESEL AREA. REFER NOTE 19. <br /> C7 <br /> ____ 0_ <br /> "LPS --- ; 19 <br /> 7 PREVIOUS LOCATION OF CONDUIT STUBS FOR VARIOUS DATA, 2 C/)LINE AND LOW <br /> LID EXTENDED TO NEW LLOCATIONWIRING AND CONDUIT TO BE O � W <br /> t7 <br /> / 11 32 I 20 REMOVE DISCONNECTS AND ALL ASSOCIATED CONDUIT AND Q M W <br /> I I CONDUCTORS SERVING WASHING AND DRYING MACHINES BACK ' ` CV W <br /> LP5(E) o I I TO ELECTRICAL PANELS. U cV } C) <br /> 11 I10 21 ROUTE TO EXISTING 30A/2P CIRCUIT BREAKER SERVING ~ - <br /> REMOVED EQUIPMENT. VERIFY BREAKER DOES NOT SERVE ANY D U O <br /> J "96" I�� I I I EXISTING LOADS BEFORE CONNECTION. Z z W <br /> 22 ROUTE TO EXISTING 20A/1P CIRCUIT BREAKER SERVING O w 0 C) <br /> 0�11 I I DIESEL DESK REMOVED EQUIPMENT. VERIFY BREAKER DOES NOT SERVE ANY O � <br /> EXISTING LOADS BEFORE CONNECTION. <br /> ©3 TIE INTO EXISTING CIRCUIT SERVING RECEPTACLES IN 0 om <br /> II I GFACr / ROOMS. 0) o <br /> II 2 <br /> ENLARGED P ©4 REFER TO PANEL SCHEDULES FOR PANEL INFORMATION. M <br /> ❑ — 9 ff- f- f� COORDINATE MOUNTING WITH OTHER ELECTRICAL COMPONENTS <br /> � E211 SCALE 1/8 1 0 NORTH IN THE AREA. MA I NTA I N REQUIRED CLEARANCES. <br /> �_ J <br /> _LLIL p-1—� I I 25 ROUTE TO EXISTING 100A/3P CIRCUIT BREAKER SERVING <br /> —�I REMOVED DRYER. <br /> r ROUTE TO EXISTING 15A/3P CIRCUIT BREAKER SERVING W <br /> _j l I ❑ II KSG I II II I I REMOVED WASHER. � <br /> EMMA ROUTE TO EXISTING 20A/1 P CIRCUIT BREAKER VACATED D <br /> DURING DEMOLITION WORK. 0) <br /> m <br /> O <br /> GENERAL ELECTRICAL NOTESi <br /> 1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME <br /> II I li 1 II I RUNS WITH INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE ISSUE BLOCK <br /> CIRCUITS (MAXIMUM OF THREE PHASE CONDUCTORS) MAY BE <br /> I/ J "LP <br /> 6" I GROUPED IN A SINGLE CONDUIT. WHERE MULTIPLE CIRCUITS <br /> 23 <br /> I/ J II 21' ARE LOCATED IN THE SAME RACEWAY, JUNCTION BOX OR NO. DATE DESCRIPTION <br /> 11 II I ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED TO <br /> �_ �t_L �I I / I INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. <br /> /F <br /> / r—I I 1 � DinII I I 2. ALL HOMERUNS ARE TO BE (2)#12, #12G IN 3/4"C UNLESS <br /> milli <br /> NOTED OTHERWISE IN FEEDER OR PANEL SCHEDULE. <br /> (J� I 3. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) <br /> SHALL BE LIMITED TO TWO OUTLET BOXES PER STUD SPACE. <br /> 4. PROVIDE ALL ISOLATED GROUND CIRCUITS WITH INDIVIDUAL <br /> L� SII I NEUTRAL CONDUCTORS AND EQUIPMENT GROUND CONDUCTORS. <br /> BRANCH CIRCUIT 8c FEEDER SCHEDULE. <br /> / O (3)#3, #8G, 1.25"C <br /> O (3)#12, #12G, 0.75"C <br /> O (3)#10, #10G, 0.75"C <br /> l CHECKED BY: BJK <br /> s 0 2 4 L LJ DRAWN BY: JHF <br /> II — II <br /> 111 COCOOLERNDENSER Q 0 0 DOCUMENT DATE: 09/01/2020 <br /> II (ON ROOF) <br /> "LP6" "LpG' EVAPORATOR EVAPORATOR <br /> 111 `YD r►a PROTO TYPE: <br /> 25 17 <br /> "LP6"� \ti 3 4 `� � 3 4 i PROTO CYCLE: <br /> I I 12,14,16 O 2 <br /> N <br /> �'-� "LP6" "LP6" <br /> CONDENSER 18,20,22 3m 1 2 4,6 1 <br /> 7-1 3 4 <br /> (ON ROOF) PROFESSIONAL SEAL <br /> 2 <br /> J II 10 JWP 7 JWP <br /> —Ji 7 <br /> "LPG' <br /> 5G, Q�OFESS/ON <br /> i , O 13 BASPG FSG' <br /> II JEJ I I I I I I I I)i I H 11111111111 <br /> o= o—= ``� -'No. E-17170 m M <br /> — 0 --- s � Exp. 12-31-21 � <br /> ElI , ��, fCTRF OF rs► IFO^s> n @ <br /> J a m. <br /> a.> <br /> _— — James R.Basqu tt - ean>�>�" <br /> — - asa <br /> POWER PLAN <br /> 1 POWER PLAN <br /> E211 SCALE- 3/16"-T-O" NORTH <br /> SHEET: <br /> E211 <br /> Copyright Notice:This tlrawing was preparal for se-a specific site contemporaneously with <br /> BRR Original printed on recycled paper is issue date and itis not—table f—se on a different project site or at a later time.use of this <br /> drawing for reference or example oanother project requires the services of properly licensed <br /> architects and engineers.Reproduction of this drawing for reuse on another project is not <br /> authorized and may be contrary to the law. <br />