2019 CALIFORNIA GREEN BUILDING STANDARDS CODE
<br /> Y YES
<br /> N/A APPLICABLE
<br /> RESPON.PARTY RESPONSIBLE
<br /> PARTY(ie:ARCHITECT,ENGINEER,NONRESIDENTIAL MANDATORY MEASURES ' SHEET 2 ( anus� 2020� Includes August 2019 Supplement) OWNERCONTRACTOR,INSPECTOR ETC.)
<br /> EX - EXSTNG O REMAIN
<br /> Y N/A a Y N/A RESPON. Y N/A RESPON. Y N/A RESPON.
<br /> w a PARTY PARTY PARTY
<br /> rY
<br /> Architect of Record:
<br /> SECTION 5.407 WATER RESISTANCE AND MOISTURE MANAGEMENT ❑ ® EX 5.410.2 COMMISSIONING. [N] New buildings 10,000 square feet and over. For new buildings 10,000 square feet 5.410.4.4 Reporting. After completion of testing, adjusting and balancing, provide a final report of testing Mariah B.Meyer
<br /> 5.303.3.4 Faucets and fountains. 5.407.1 WEATHER PROTECTION. Provide a weather-resistant exterior wall and foundation envelope as required by and over, building commissioning shall be included in the design and construction processes of the building project to signed by the individual responsible for performing these services. 8131 Metcalf Avenue
<br /> California Building Code Section 1402.2 (Weather Protection), manufacturer's installation instructions or local verify that the building systems and components meet the owner's or owner representative's project Suite 300
<br /> ordinance, whichever is more stringent. requirements. Commissioning shall be performed in accordance with this section b trained personnel with experience Overland Park,KS 66204
<br /> more than
<br /> Nonresidential Lavatory faucets. Lavatory faucets shall have a maximum flow rate of not g q g p Y p p 5.410.4.5 Operation and maintenance(O&M)manual. Provide the building owner or representative with
<br /> on projects of comparable size and complexity. For I-occupancies that are not regulated by OSHPD or for www.brrarch.com
<br /> more than 0.5 gallons per minute at 60 psi.
<br /> ® ❑ detailed operating and maintenance instructions and copies of guaranties/warranties for each system. O& M ARCH 5.407.2 MOISTURE CONTROL. Employ moisture control measures by the following methods. I-occupancies and L-occupancies that are not regulated y the California Energy Code Section 100.0 Scope, all instructions shall be consistent with OSHA requirements in CCRTitle 8Section 5142and other related Tel:913-262-9095
<br /> , , ,
<br /> 5.303.3.4.2 Kitchen faucets. Kitchen faucets shall have a maximum flow rate of not more than 1.8 requirements in Sections 5.410.2 through 5.410.2.6 shall apply. Fax:913-262-9044
<br /> gallons per minute at 60 psi. Kitchen faucets may temporarily increase the flow above the maximum rate, 5.407.2.1 Sprinklers. Design and maintain landscape irrigation systems to prevent spray on structures. regulations.
<br /> but not to exceed 2.2 gallons per minute at 60 psi, and must default to a maximum flow rate of 1.8 gallons Note: For energy-related systems under the scope(Section 100)of the California Energy Code, including heating,
<br /> per minute at 60 psi. 5.407.2.2 Entries and openings. Design exterior entries and/or openings subject to foot traffic or wind-driven ventilation, air conditioning (HVAC)systems and controls, indoor lighting systems and controls, as well as water 5.410.4.5.1 Inspections and reports. Include a copy of all inspection verifications and reports required
<br /> rain to prevent water intrusion into buildings as follows: heating systems and controls, refer to California Energy Code Section 120.8 for commissioning requirements by the enforcing agency.
<br /> 5.303.3.4.3 Wash fountains.Wash fountains shall have a maximum flow rate of not more thanl.8 .�
<br /> gallons per minute/20 rims ace Inches at 60 sl 5.407.2.2.1 Exterior door protection. Primary exterior entries shall be covered to prevent water Commissioning requirements shall include: L <N z �,o
<br /> intrusion by using nonabsorbent floor and wall finishes within at least 2 feet around and perpendicular to DIVISION 5.5 ENVIRONMENTAL QUALITY w L,0Z F F W H LL W O
<br /> 5.303.3.4.4 Metering faucets. Metering faucets shall not deliver more than 0.20 gallons per cycle. such openings plus at least one of the following: 1. Owner's or Owner representative's project requirements. SECTION 5.501 GENERAL z LL w a _0 o 0
<br /> 2. Basis of design. � aa�EDoQoW°WoWow
<br /> 5.303.3.4.5 Metering faucets for wash fountains. Metering faucets for wash fountains shall have a 1. An installed awning at least 4 feet in depth. 3. Commissioning measures shown in the construction documents. 5.501.1 SCOPE. The provisions of this chapter shall outline means of reducing the quantity of air contaminants that O a F J o Z a L 0 o a S 2>
<br /> 9 9LL
<br /> maximum flow rate of not more than 0.20 gallons per minute/20 [rim space(inches)at 60 psi]. 2. The door is protected by a roof overhang at least 4 feet in depth. 4. Commissioning plan. are odorous, irritating, and/or harmful to the comfort and well-being of a building's installers,occupants and neighbors. Z �, a o a Z o-fd-_w >,
<br /> 3. The door is recessed at least 4 feet. 5. Functional performance testing. O �LL W R D o<,Z W W 0 2 W z
<br /> Note: Where complying faucets are unavailable, aerators or other means may be used to achieve 4. Other methods which provide equivalent protection. 6. Documentation and training. SECTION 5.502 DEFINITIONS Z a o o W=J w Z o
<br /> 7. Commissioning report. 5.502.1 DEFINITIONS. The following terms are defined in Chapter 2 (and are included here for reference) Q g o LL = i z a N a
<br /> reduction. g p ❑ XZMZJU~iQ�W��W Kw
<br /> 5.407.2.2.2 Flashing. Install flashings integrated with a drainage plane. o o F o co w o x a Z X o=
<br /> Exceptions: ARTERIAL HIGHWAY.A general term denoting a highway primarily for through traffic usually on a continuous route. F _ o a�o W o z U-)0 P o
<br /> 5.303.4 COMMERCIAL KITCHEN EQUIPMENT.
<br /> A-WEIGHTED SOUND LEVEL(dBA).The sound pressure level in decibels as measured on a sound level meter
<br /> SECTION 5.408 CONSTRUCTION WASTE REDUCTION, DISPOSAL AND 1. Unconditioned warehouses of any size.
<br /> a 5.303.4.1 Food Waste Disposers. Disposers shall either modulate the use of water to no more than 1 gpm 2. Areas less than 10,000 square feet used for offices or other conditioned accessory spaces within using the internationally standardized A-weighting filter or as computed from sound spectral data to which A-weighting
<br /> when the disposer is not in use not active) grinding food waste/no-load or shall automatics)) shut off after no
<br /> RECYCLING adjustments have been made.
<br /> p ( Y g g ) Y ® ❑ GC unconditioned warehouses.
<br /> more than 10 minutes of inactivity. Disposers shall use no more than 8 gpm of water. 5.408.1 CONSTRUCTION WASTE MANAGEMENT. Recycle and/or salvage for reuse a minimum of 65%of the 3. Tenant improvements less than 10,000 square feet as described in Section 303.1.1. CONSULTANT LOGO
<br /> Note: This code section does not affect local jurisdiction authority to prohibit or require disposer non-hazardous construction and demolition waste in accordance with Section 5.408.1.1, 5.408.1.2 or 5.408.1.3;or 4. Open parkin garages of an size, or open parkin garage areas, of an size,within a structure. 1 BTU/HOUR. British thermal units per hour, also referred to as Btu. The amount of heat required to raise one pound
<br /> installation. meet a local construction and demolition waste management ordinance,whichever is more stringent. g g g y g g g Y of water one degree Fahrenheit per hour, a common measure of heat transfer rate. A ton of refrigeration is 12,000 Btu,
<br /> Note: For the purposes of this section, unconditioned shall mean a building, area, or room which does not the amount of heat required to melt a ton (2,000 pounds)of ice at 320 Fahrenheit.
<br /> ® ❑ 5.303.5 AREAS OF ADDITION OR ALTERATION. For those occupancies within the authority of the California 5.408.1.1 Construction waste management plan.Where a local jurisdiction does not have a construction and provide heating and or air conditioning.
<br /> J Building Standards Commission as specified in Section 103,the provisions of Section 5.303.3 and 5.303.4 shall apply demolition waste management ordinance, submit a construction waste management plan that: COMMUNITY NOISE EQUIVALENT LEVEL(CNEL). A metric similar to the day-night average sound level (Ldn),
<br /> a to new fixtures in additions or areas of alteration to the building. Informational Notes: except that a 5 decibel adjustment is added to the equivalent continuous sound exposure level for evening hours(7pm
<br /> 1. Identifies the construction and demolition waste materials to be diverted from disposal by efficient to 10pm)in addition to the 10 dB nighttime adjustment used in the Ldn.
<br /> ® ❑ m 5.303.6 STANDARDS FOR PLUMBING FIXTURES AND FITTINGS. Plumbing fixtures and fittings shall be installed usage, recycling, reuse on the project or salvage for future use or sale. 1. IAS AC 476 is an accreditation criteria for organizations providing training and/or certification of
<br /> in accordance with the California Plumbing Code, and shall meet the applicable standards referenced in Table 1701.1 2. Determines if construction and demolition waste materials will be sorted on-site(source-separated)or commissioningpersonnel. AC 476 is available to the AuthorityHavingJurisdiction as a reference for in WOOD PRODUCTS. Composite wood products include hardwood plywood, particleboard and medium
<br /> a of the California Plumbing Code and in Chapter 6 of this code. bulk mixed (single stream). qualifications of commissioning personnel.AC 476 des not certify individuals to conduct functional density fiberboard. "Composite wood products"does not include hardboard, structural plywood, structural
<br /> 3. Identifies diversion facilities where construction and demolition waste material collected will be taken. performance tests or to adjust and balance systems. panels, structural composite lumber, oriented strand board, glued laminated timber,timber, prefabricated wood 1-joists
<br /> 4. Specifies that the amount of construction and demolition waste materials diverted shall be calculated or finger jointed lumber, all as specified in California Code of Regulations(CCR),Title 17, Section 93120.1(a).
<br /> byweight or volume, but not by both. 2. Functional performance testing for heating, ventilation, air conditioning systems and lighting controls
<br /> SECTION 5.304 OUTDOOR WATER USE must be performed in compliance with the California Energy Code. Note: See CCR, Title 17, Section 93120.1.
<br /> ❑ ® EX 5.304.1 OUTDOOR POTABLE WATER USE IN LANDSCAPE AREAS. Nonresidential developments shall comply 5.408.1.2 Waste Management Company. Utilize a waste management company that can provide verifiable
<br /> with a local water efficient landscape ordinance or the current California Department of Water Resources'Model Water documentation that the percentage of construction and demolition waste material diverted from the landfill DAY-NIGHT AVERAGE SOUND LEVEL(Ldn).The A-weighted equivalent continuous sound exposure level for a w
<br /> Efficient Landscape Ordinance (MWELO),whichever is more stringent. complies with this section. 5.410.2.1 Owner's or Owner Representative's Project Requirements(OPR). [N] The expectations and
<br /> 24-hour period with a 10 dB adjustment added to sound levels occurring during nighttime hours(10p.m.to 7 a.m.). Q Z
<br /> requirements of the building appropriate to its phase shall be documented before the design phase of the DECIBEL 0 o
<br /> Notes: Note: The owner or contractor shall make the determination if the construction and demolition waste material (db).A measure on a logarithmic scale of the magnitude of a particular quantity(such as sound pressure, O Q
<br /> project begins. This documentation shall include the following: �
<br /> 1. The Model Water Efficient Landscape Ordinance MWELO Is located in the California Code of Regulations, will be diverted b a waste management company. sound power, sound intensity)with respect to a reference quantity. U) U
<br /> p (MWELO) g Y g p Y 1. Environmental and sustainability goals. O
<br /> Title 23, Chapter 2.7, Division 2. a- _J
<br /> 2. Building sustainable goals. UJ w
<br /> 2. MWELO and supporting documents, including a water budget calculator, are available at: Exceptions to Sections 5.408.1.1 and 5.408.1.2: 3. Indoor environmental quality requirements. ELECTRIC VEHICLE(EV).An automotive-type vehicle for on-road use, such as passenger automobiles, buses, � X
<br /> https://www.water.ca.gov/. trucks, vans, neighborhood electric vehicles, electric motorcycles, and the like, primarily powered by an electric motor a- Y
<br /> 4. Project program, including facility functions and hours of operation, and need for after hours = U)
<br /> 1. Excavated soil and land-clearing debris. operation. that draws current from a rechargeable storage battery, fuel cell, photovoltaic array, or other source of electric current. O w w
<br /> ❑ ® EX 5.304.6 OUTDOOR POTABLE WATER USE IN LANDSCAPE AREAS. For public schools and community colleges, 2. Alternate waste reduction methods developed by working with local agencies if diversion or recycle 5. E Equipment ment and s stems ex ectations. Plug-in hybrid electric vehicles (PHEV)are considered electric vehicles. For purposes of the California Electrical Code, ❑
<br /> landscape projects as described in Sections 5.304.6.1 and 5.304.6.2 shall comply with the California Department of facilities capable of compliance with this item do not exist. 5. Building nt a a t and operation and maintenance O&M personnel expectations. off-road, self-propoelled electric vehicles, such as industrial trucks, hoists, lifts,transports, golf carts,airline ground IX w
<br /> Water Resources Model Water Efficient Landscape Ordinance(MWELO)commencing with Section 490 of Chapter 3. Demolition waste meeting local ordinance or calculated in consideration of local recycling facilities g p p ( )p p support equipment,tractors, boats, and the like,are not included. N w w
<br /> gn(BOD). [N] A written explanation of how the design of the building systems meets
<br /> 2.7, Division 2, Title 23, California Code of Regulations, except that the evapotranspiration adjustment factor(ETAF) and markets. 5.410.2.2 Basis of DesiU N p
<br /> shall be 0.65 with an additional water allowance for special landscape areas(SLA)of 0.35. ELECTRIC VEHICLE CHARGING STATION(S)(EVCSj). One or more spaces intended for charging electric vehicles.
<br /> the OPR shall be completed at the design phase of the building project. The Basis of Design document shall z O
<br /> 5.408.1.3 Waste stream reduction alternative. The combined weight of new construction disposal that does cover the following systems: ~
<br /> Exception: Any project with an aggregate landscape area of 2,500 square feet or less may comply with the not exceed two pounds per square foot of building area may be deemed to meet the 65%minimum requirement ELECTRIC VEHICLE SUPPLY EQUIPMENT(EVSE).The conductors, including the ungrounded, grounded, and Z L
<br /> prescriptive measures contained in Appendix D of the MWELO. as approved by the enforcing agency. 1. Renewable energy systems. equipment grounding conductors and the electric vehicle connectors, attachment plugs, and all other fittings, devices, O W O ❑
<br /> power outlets, or apparatus installed specifically for the purpose of transferring energy between the premises wiring O Ix ❑
<br /> 2. Landscape irrigation systems. � a- Q
<br /> 5.304.6.1 Newly constructed landscapes. New construction projects with an aggregate landscape 5.408.1.4 Documentation. Documentation shall be provided to the enforcing agency which demonstrates 3. Water reuse system. and the electric vehicle. O
<br /> area equal to or greater than 500 square feet. compliance with Sections 5.408.1.1,through 5.408.1.3. The waste management plan shall be updated as om
<br /> necessary and shall be accessible during construction for examination b the enforcing agency. ENERGY EQUIVALENT(NOISE)LEVEL(Leq).The level of a steady noise which would have the same energy as N
<br /> rY 9 Y g5.410.2.3 Commissioning plan. [N] Prior to permit issuance a commissioning plan shall be completed to N
<br /> 5.304.6.2 Rehabilitated landscapes. Rehabilitated landscape projects with an aggregate the fluctuating noise level integrated over the time of period of interest. o
<br /> document how the project will be commissioned. The commissioning plan shall include the following: N
<br /> landscape area equal to or greater than 1,200 square feet. Notes: 1. General project information. co
<br /> 2. Commissioning goals. EXPRESSWAY.An arterial highway for through traffic which may have partial control of access, but which may or may
<br /> 1. Sample forms found in "A Guide to the California Green Building Standards Code(Nonresidential)" 3. Systems to be commissioned. Plans to test systems and components shall include: not be divided or have grade separations at intersections.
<br /> located at www.bsc.ca.gov/Home/CALGreen.aspx may be used to assist in documenting compliance a. An explanation of the original design intent.
<br /> DIVISION 5.4 MATERIAL CONSERVATION AND RESOURCE with the waste management plan. b. Equipment and systems to be tested, including the extent of tests. FREEWAY.A divided arterial highway with full control of access and with grade separations at intersections. w
<br /> 2. Mixed construction and demolition debris processors can be located at the California Department of c. Functions to be tested. Co
<br /> EFFICIENCY Resources Recycling and Recovery(CalRecycle). d. Conditions under which the test shall be performed. GLOBAL WARMING POTENTIAL(GWP).The radiative forcing impact of one mass-based unit of a given greenhouse
<br /> e. Measurable criteria for acceptable performance. gas relative to an equivalent unit of carbon dioxide over a given period of time. Carbon dioxide is the reference Z
<br /> ® ❑ GC 5.408.2 UNIVERSAL WASTE. [A] Additions and alterations to a building or tenant space that meet the scoping 4. Commissioning team information. compound with a GWP of one. m
<br /> SECTION 5.401 GENERAL provisions in Section 301.3 for nonresidential additions and alterations, shall require verification that Universal Waste 5. Commissioning process activities, schedules and responsibilities. Plans for the completion of 3
<br /> 5.401.1 SCOPE. The provisions of this chapter shall outline means of achieving material conservation and resource items such as fluorescent lamps and ballast and mercury containing thermostats as well as other California prohibited commissioningshall be included. GLOBAL WARMING POTENTIAL VALUE(GWP VALUE).A 100-year GWP value published by the
<br /> efficiency through protection of buildings from exterior moisture, construction waste diversion, employment of Universal Waste materials are disposed of properly and are diverted from landfills. A list of prohibited Universal Waste Intergovernmental Panel on Climate Change(IPCC) in either its Second Assessment Report(SAR)(IPCC, 1995); or
<br /> techniques to reduce pollution through recycling of materials, and building commissioning or testing and adjusting. materials shall be included in the construction documents. 5.410.2.4 Functional performance testing. [N] Functional performance tests shall demonstrate the correct its Fourth Assessment A-3 Report(AR4)(IPCC, 2007). The SAR GWP values are found in column"SAR(100-yr)"of installation and operation of each component, system and system-to-system interface in accordance with the Table 2.14.;the AR4 GWP values are found in column 100 yr"of Table 2.14. ISSUE BLOCK
<br /> Note: Refer to the Universal Waste Rule link at: approved plans and specifications. Functional performance testing reports shall contain information addressing NO. DATE DESCRIPTION
<br /> SECTION 5.402 DEFINITIONS http://www.dtsc.ca.gov/LawsRegsPolicies/Regs/upload/OEAR-A_REGS_UWR_FinalText.pdf each of the building components tested,the testing methods utilized, and include any readings and adjustments HIGH-GWP REFRIGERANT.A compound used as a heat transfer fluid or gas that is: (a)a chlorofluorocarbon, a
<br /> 5.402.1 DEFINITIONS. The following terms are defined in Chapter 2 (and are included here for reference) made. hdrochlorofluorocarbon, a hydrofluorocarbon, a perfluorocarbon, or any compound or blend of compounds,with a
<br /> ® ❑ GC 5.408.3 EXCAVATED SOIL AND LAND CLEARING DEBRIS. 100 percent of trees, stumps, rocks and associated GWP value equal to or greater than 150, or(B)any ozone depleting substance as defined in Title 40 of the Code of
<br /> ADJUST. To regulate fluid flow rate and air patterns at the terminal equipment, such as to reduce fan speed or adjust vegetation and soils resulting primarily from land clearing shall be reused or recycled. For a phased project,such Federal Regulations, Part 82, sec.82.3 (as amended March 10,2009).
<br /> a damper. material may be stockpiled on site until the storage site is developed. 5.410.2.5 Documentation and training. [N] A Systems Manual and Systems Operations Training are required,
<br /> including Occupational Safety and Health Act(OSHA)requirements in California Code of Regulations(CCR), LONG RADIUS ELBOW. Pipe fitting installed between two lengths of pipe or tubing to allow a change of direction,
<br /> BALANCE. To proportion flows within the distribution system, including sub-mains, branches and terminals, Exception: Reuse, either on or off-site, of vegetation or soil contaminated by disease or pest infestation. Title 8, Section 5142, and other related regulations. with a radius 1.5 times the pipe diameter.
<br /> according to design quantities.
<br /> Notes: 5.410.2.5.1 Systems manual. [N] Documentation of the operational aspects of the building shall be LOW-GWP REFRIGERANT.A compound used as a heat transfer fluid or gas that: (A)has a GWP value less than
<br /> a) BUILDING COMMISSIONING. A systematic quality assurance process that spans the entire design and construction completed within the systems manual and delivered to the building owner or representative.The 150, and (B)is not an ozone depleting substance as defined in Title 40 of the Code of Federal Regulations, Part 82,
<br /> �
<br /> process, including verifying and documenting that building systems and components are planned,designed, installed, 1. If contamination by disease or pest infestation is suspected, contact the County Agricultural systems manual shall include the following: sec.82.3 (as amended March 10,2009).
<br /> tested, operated and maintained to meet the owner's project requirements. Commissioner and follow its direction for recycling or disposal of the material. 1. Site information, including facility description, history and current requirements.
<br /> N 2. For a map of know pest and/or disease quarantine zones, consult with the California Department of 2. Site contact information. MERV. Filter minimum efficiency reporting value, based on ASHRAE 52.2-1999.
<br /> `V ORGANIC WASTE. Food waste, green waste, landscape and pruning wste, nonhazardous wood waste, and food Food and Agriculture. (www.cdfa.ca.gov)
<br /> 3. Basic operations and maintenance, including general site operating procedures, basic
<br /> � soiled paper waste that is mixed in with food waste. MAXIMUM INCREMENTAL REACTIVITY(MIR).The maximum change in weight of ozone formed by adding a
<br /> U) troubleshooting, recommended maintenance requirements, site events log. compound to the"Base REactive Organic Gas (ROG) Mixture" per weight of compound added, expressed to
<br /> 4. Major systems. s
<br /> � TEST. A procedure to determine quantitative performance of a system or equipment SECTION 5.410 BUILDING MAINTENANCE AND OPERATIONS 1 y hundreths of a gram (g O /g ROC).
<br /> U ® ❑ DWNEF 5.410.1 RECYCLING BY OCCUPANTS. Provide readily accessible areas that serve the entire building and are 5. Site equipment inventory and maintenance notes. CHECKED BY:
<br /> = identified for the depositing, stora e and collection of non-hazardous materials for recycling, includin at a minimum 6. A copy of verifications required by the enforcing agency or this code. PRODUCT-WEIGHTED MIR PWMIR .The sum of all weighted-MIR for all ingredients in a product subject to this
<br /> U g • g ( ) ( ) g g p 1
<br /> paper, corrugated cardboard, glass, plastics, organic waste, and metals or meet a lawfully enacted local recycling 7. Other resources and documentation, if applicable. article. The PWMIR is the total product reactivity expressed to hundredths of a gram of ozone formed per gram of DRAWN BY: NC
<br /> Z ordinance, if more restrictive. product(excluding container and packaging).
<br /> w
<br /> w 5.410.2.5.2 Systems operations training. [N] A program for training of the appropriate maintenance DOCUMENT DATE: 09/01/20
<br /> 01� Exception: Rural jurisdictions that meet and apply for the exemption in Public Resources PSIG. Pounds per square inch, guage.
<br /> CD staff for each equipment type and/or system shall be developed and documented in the commissioning
<br /> Code 42649.82 (a)(2)(A)et seq. shall also be exempt from the organic waste portion of this section.
<br /> Q report and shall include the following: PROTO TYPE: REMODEL
<br /> U 1. System/equipment overview(what it is,what it does and with what other systems and/or REACTIVE ORGANIC COMPOUND (ROC). Any compound that has the potential, once emitted,to contribute to
<br /> 5.410.1.1 Additions. All additions conducted within a 12-month period under single or multiple permits, ozone formation in the troposphere.
<br /> o resulting in an increase of 30%or more in floor area, shall provide recycling areas on site. equipment it interfaces). PROTO CYCLE: 2020 QUARTER 1
<br /> 0 2. Review and demonstration of servicing/preventive maintenance. SCHRADER ACCESS VALVES.Access fittings with a valve core installed.
<br /> Exception: Additions within a tenant space resulting in less than a 30% increase in the tenant space 3. Review of the information in the Systems Manual.
<br /> F_ floor area. 4. Review of the record drawings on the system/equipment. SHORT RADIUS ELBOW. Pipe fitting installed between two lengths of pipe or tubing to allow a change of direction, PROFESSIONAL SEAL
<br /> o with a radius 1.0 times the pipe diameter.
<br /> 5.410.1.2 Sample ordinance. Space allocation for recycling areas shall comply with Chapter 18, Part 3, 5.410.2.6 Commissioning report. [N]A report of commissioning process activities undertaken through the
<br /> Division 30 of the Public Resources Code. Chapter 18 is known as the California Solid Waste Reuse and SUPERMARKET. For the purposes of Section 5.508.2, a supermarket is any retail food facility with 8,000 square feet
<br /> Recycling Access Act of 1991 (Act). design and construction phases of the building project shall be completed and provided to the owner or or more conditioned area, and that utilizes either refrigerated display cases, or walk-in coolers or freezers connected
<br /> j representative. to remote compressor units or condensing units.
<br /> o Note: A sample ordinance for use by local agencies may be found in Appendix A of the document at the
<br /> Q CalRecycle's web site. ® ❑ MECH 5.410.4 TESTING AND ADJUSTING. New buildings less than 10,000 square feet.Testing and adjusting of VOC.A volatile organic compound broadly defined as a chemical compound based on carbon chains or rings with
<br /> U systems shall be required for new buildings less than 10,000 square feet or new systems to serve an addition or vapor pressures greater than 0.1 millimeters of mercury at room temperature. These compounds typically contain
<br /> alteration subject to Section 303.1. hydrogen and may contain oxygen, nitrogen and other elements. See CCR Title 17, Section 94508(a) J MAS 11►N �►
<br /> MEYER
<br /> j Note: Where specific regulations are cited from different agencies such as SCAQMD,ARB, etc.,the VOC definition * C 440
<br /> 0 5.410.4.2 (Reserved) included in that specific regulation is the one that prevails for the specific measure in question. J12M
<br /> 00 Note: For energy-related systems under the scope (Section 100)of the California Energy Code, including SECTION 5.503 FIREPLACES S'
<br /> L N heating, ventilation, air conditioning (HVAC)systems and controls, indoor lighting system and controls, as well ❑ ® 5.503.1 FIREPLACES. Install only a direct-vent sealed-combustion gas or sealed wood-burning fireplace,or a sealed
<br /> 0 as water heating systems and controls, refer to California Energy Code Section 120.8 for commissioning woodstove or pellet stove, and refer to residential requirements in the California Energy Code,Title 24, Part 6,
<br /> requirements and Sections 120.5, 120.6, 130.4, and 140.9(b)3 for additional testing requirements of specific Subchapter 7, Section 150. Woodstoves, pellet stoves and fireplaces shall comply with applicable local ordinances.
<br /> c N systems.
<br /> 5.503.1.1 Woodstoves. Woodstoves and pellet stoves shall comply with U.S. EPA New Source Performance
<br /> �
<br /> Q 5.410.4.2 Systems. Develop a written plan of procedures for testing and adjusting systems. Systems to be Standards (NSPS)emission limits as applicable, and shall have a permanent label indicating they are certified
<br /> v included for testing and adjusting shall include at a minimum, as applicable to the project: to meet the emission limits.
<br /> I ,=
<br /> 0 1. Renewable energy systems.
<br /> 2. Landscape irrigation systems. SECTION 5.504 POLLUTANT CONTROL /'�
<br /> 3. Water reuse systems. ® ❑ GC 5.504.1 TEMPORARY VENTILATION. The permanent HVAC system shall only be used during construction if C A L V R E E N
<br /> N necessary to condition the building or areas of addition or alteration within the required temperature range for
<br /> 60- and equipment installation. If the HVAC system is used during construction, use return air filters with a CHECKLIST
<br /> 5.410.4.3 Procedures. Perform testing and adjusting procedures in accordance with manufacturer's Minimum Efficiency Reporting Value (MERV)of 8, based on ASHRAE 52.2-1999, or an average efficiency of
<br /> specifications and applicable standards on each system. 30% based on ASHRAE 52.1-1992 Replace all filters immediately prior to occupancy, or, if the building is
<br /> O > occupied during alteration, at the conclusion of construction.
<br /> No 5.410.4.3.1 HVAC balancing. In addition to testing and adjusting, before a new space-conditioning
<br /> NN ~ system serving a building or space is operated for normal use,the system shall be balanced in ® ❑ GC 5.504.3 Covering of duct openings and protection of mechanical equipment during construction.At the time of
<br /> _ 0 accordance with the procedures defined by the Testing Adjusting and Balancing Bureau National rough installation and during storage on the construction site until final startup of the heating,cooling and ventilation SHEET:
<br /> M > Standards;the National Environmental Balancing Bureau Procedural Standards;Associated Air Balance equipment, all duct and other related air distribution component openings shall be covered with tape, plastic,
<br /> 7 j Council National Standards or as approved by the enforcing agency. sheetmetal or other methods acceptable to the enforcing agency to reduce the amount of dust,water and debris which G007
<br /> may enter the system.
<br /> z0 oil 0 oil 0
<br /> Copyright Notice:Th's dm,,g was pmp,md for use on a spectt ste contemporane,,IN wth
<br /> BRR Original printed on recycled paper 's issue date and t s not suitable for use on a d'rferent project ste or at a later tme.use of this
<br /> d..tg for reference o amph on another project requ'res the ser,les of property f en,,d
<br /> arch'tec[s and engineers.Reproduc[en of th's drawing for reuse on another project's not
<br />
|