MECHANICAL LEGEND
<br />GRILLE SCHEDULE
<br />SYMBOL
<br />DESCRIPTION
<br />DESORPTION
<br />E�L__
<br />DETAIL NUMBER
<br />Ell DO PRESS.
<br />SHEET ON WHICH DETAIL IS FOUND
<br />R
<br />DUCT RISE
<br />D
<br />DUCT DROP
<br />----4 OSA
<br />OUTSIDE AIR
<br />—� $A
<br />SUPPLY AIR
<br />RA
<br />RETURN AIR
<br />+—BD
<br />BALANCE DAMPER
<br />2910
<br />DIAMETER OR PHASE
<br />1
<br />e
<br />FLEXIBLE DUCT
<br />12x10
<br />DUCT - DIMENSION SHOWN X WIDTH OR HEIGHT NOT SHOWN
<br />12x10L
<br />ACOUSTICAL LINED DUCTING
<br />—�—
<br />DUCT TRANSITION
<br />®
<br />SUPPLY AIR DIFFUSER, RETURN OR EXHAUST AIR GRILLE
<br />T
<br />THEF410STAT
<br />405
<br />RELOCATE
<br />MD
<br />MOTORIZED DAMPER
<br />300
<br />EXISTING PIPING: OR FIXTURE TO BE REMOVED OR ABANDONED IN PLACE
<br />X X X
<br />-� -111- POG
<br />POINT OF CONNECTION
<br />ABC
<br />ABOVE CEILING
<br />AE
<br />AIR EXTRACTOR
<br />AFF
<br />ABOVE FINISHED FLOOR
<br />AFG
<br />ABOVE FINISHED GRADE
<br />AP
<br />ACCESS PANEL
<br />UCD
<br />UNDER CUT DOOR
<br />CD
<br />CONDENSATE DRAIN
<br />CW,/
<br />CUBIC FEET OF AIRFLOW PER MINUTE
<br />CLG.
<br />CEILING
<br />(E), EXISTING
<br />EXISTING TO BE FIELD VERIFIED BY CONTRACTC R
<br />FA, TA
<br />FROM ABOVE, TO ABOVE
<br />FB, TB
<br />FROM BELOW, TO BELOW
<br />FC
<br />FLEXIBLE CONNECTION
<br />FF.
<br />FINISHED FLOOR
<br />o---
<br />FIRE SMOKE DAMPER
<br />/FT
<br />PER FOOT
<br />(N)
<br />NEW
<br />NIMC
<br />NOT IN MECHANICAL CONTRACT
<br />N.T.S.
<br />NOT TO SCALE
<br />OBD.
<br />OPPOSED BLADE DAMPER
<br />REF
<br />REFERENCE
<br />®
<br />SMOKE DETECTOR
<br />TYP.
<br />TYPICAL
<br />GENERAL MECHAMOAL NOTES
<br />ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND SHALL BE EQUAL IN
<br />QUALITY, TYPE, CAPACITY EFFICIENCY AND ACCESSORIES TO THE EQUIPMENT
<br />NOTED ON THE DRAWINGS. ADJUSTMENTS TO CONSTRUCTION AND ACCESSORIES
<br />ON SUBSTITUTED EQUIPMENT MAY BE REQUIRED TO ACHIEVE THIS EQUALITY, AND
<br />SHALL BE INCLUDED AT NO EXTRA COST TO THE OWNER MAKE ANY CHANGES IN
<br />DUCTWORK, PIPING, FRAMING, ETC., AS REQUIRED TO ACCOMMODATE
<br />SUBSTITUTED EQUIPMENT.
<br />2. INSTALL ALL EQUIPMENT AND MATERIALS AND PERFORM ALL WORK IN
<br />ACCORDANCE WITH ALL APPLICABLE CODES. APPLICABLE CODES SHALL
<br />INCLUDE, BUT NOT BE LIMITED TO THE LATEST EDITIONS OF THE CALIFORNAI
<br />MECHANICAL CODE, CALIFORNIA CODE OF REGULATIONS (CCR), CALIFORNIA FIRE
<br />REGULATIONS AND TITLE 24 ENERGY EFFICIENCY STANDARDS. WHERE HEAVIER
<br />GAGES OF MATERIAL, LAR3ER SIZES OR MORE STRINGENT REQUIREMENTS THAN
<br />THE CODES ARE REQUIRED BY THE CONTRACT DOCUMENTS, SUCH INCREASED
<br />REQUIREMENTS SHALL APPLY.
<br />3. FABRICATE AND INSTALL ALL DUCTWORK IN ACCORDANCE WITH THE LATEST
<br />EDITION OF SMACNA GUIDELINES FOR DUCT CONSTRUCTION AND THE CALIFORNIA
<br />MECHANICAL CODE. ALL DUCT JOINTS INCLUDING MECHANICAL FLANGED JOINTS
<br />SHALL BE SEALED WITH SILVER TAPE, OR ARABOL AND CANVAS. SEAL THE
<br />JOINTS OF ALL DUCTS EXPOSED TO THE WEATHER WITH ARA50L AND CANVAS.
<br />PROVIDE ALL BRANCH DUCTS WITH VOLUME DAMPERS WITH LOCKING QUADRANTS
<br />LOCATED AT LEAST FIVE FEET (59 FROM THE GRILLE OR DIFFUSER SERVED.
<br />4. SUPPORTS FOR ALL PIPING AND DUCTWORK SHALL BE IN ACCORDANCE WITH
<br />SMACNA "GUIDELINES FOR SEISMIC RESTRAINT OF MECHANICAL SYSTEMS".
<br />CONTRACTOR SHAD. PROVIDE CALCULATIONS FOR ISOLATORS AND MOUNTING
<br />ACCEPTABLE TO THE REVIEWING AUTHORITY WHEN REQUIRED BY SAME.
<br />5. ALL RECTANGULAR OR ROUND RIGID DUCTS SHALL BE OF SMACNA GAGE
<br />GALVANIZED STEEL OR ALUMINUM, UNLESS OTHERWISE NOTED ON THE DRAWINGS.
<br />PROVIDE FLAT SEAM CONSTRUCTION FOR ANY DUCTS EXPOSED IN OCCUPIED
<br />SPACE. NOTE_ : ALUMA-FLEX IS�L4C��P� I�Ig�gO�p�clC
<br />=
<br />6. FL x"j DUGT13 PER1MVD AND NULL BE awfm IL, 1414 LEx G-10'1 OR
<br />EQ LN FACTORY NOQ ATED. FLD(IM DUCTS 011 NOT !RE UBW 1111100
<br />WORMED DUc"Illo C OCCUFA BECURE FLEXIDLB DUCIUIORK WTH TI1R0
<br />MIMCK MCALLY APPLIED PI.A6TIC 6TRAP6 OR ONE W7Fd"I MW CLAIV
<br />—& RM(WE DUM W114 20 D�mA� �
<br />ti 81 W.
<br />1. INSULATE ALL SUPPLY AND RETURN DUCTS WITH 2" THICK, 3/4 PCF DENSITY O -C F
<br />OR EQUAL, FIBERGLASS DUCT WRAP, TYPE IV, WITH FACTORY APPLIED FLAME
<br />RETARDANT FOIL REINFORCED KRAFT FACING. LAP ALL JOINT 4" MINIMUM, AND
<br />SECURE WITH GALVANIZED STEEL WIRE.
<br />8. LINE ALL SUPPLY AND RETURN DUCT DROPS FOR A MINIMUM OF 10' FROM THE
<br />UNIT WITH I" THICK O -C F AEROFLEX TYPE 200 OR EQUAL ACOUSTIC DUCT
<br />LINER INSTALL WITH 100% COVERAGE ADHESIVE, AND FURTHER APPLY
<br />MECHANICAL PIN FASTENERS WFERE DUCT SIDE EXCEEDS 24". DUCT DIMENSIONS
<br />ARE NET INTERNAL DIMENSION. SEAL BUTT ENDS OF EXPOSED INSULATION IN THE
<br />DUCTS WITH MANUFACTURERS RECOMMENDED SEALANT OR ADHESIVE.
<br />9• CONTROLS SHALL COMPLY WITH THE LATEST EDITION OF CEG ( JULY 2016),
<br />ALL CONTROLS AND CONTROL WIRING NOT
<br />SPECIFICALLY SHOWN BUT REQUIRED FOR A COMPLETE AND WORKABLE SYSTEM
<br />SHALL BE SUPPLIED BY THE CONTRACTOR AND INSTALLED AT NO ADDITIONAL
<br />COST TO THE OWNER
<br />10. ALL AIR SYSTEMS SHALL BE BALANCED BY A QUALIFIED MECHANICAL
<br />CONTRACTOR USING AABC, SMACNA OR NEBB PROCEDURES. AIR QUANTITIES
<br />SHALL BE BALANCED TO NOT MORE THAN 10% ABOVE OR 0% BELOW THE
<br />QUANTITIES SHOUN ON THE DRAWWjS. CONTRACTOR SHALL SUBMIT A COMPLETE
<br />AIR BALANCE REPORT INDICATING, AS A MINIMUM, THE AIR DELIVERY FOR EACH
<br />DIFFUSER THE FINAL OPERATING DATA FOR THE SYSTEMS AND THE AIR
<br />CONDITIONING UNITS.
<br />11. SUBMIT FOR APPROVAL (6) COPIES OF COMPLETE SUBMITTAL DATA ON
<br />SPECIFIED AND PROPOSED EQUIPMENT AND MATERIALS. SUBMITTALS SHALL
<br />INCLUDE EQUIPMENT SIZES, CAPACITY, MOTOR LOCATIONS, PERFORMANCE
<br />CURVES AND OTHER PERTINENT DATA EACH SUBMITTAL SHALL INCLUDE
<br />IDENTIFICATION TAGS OR SYMBOLS TO MATCH DOGS. PARTIAL SUBMITTALS OR
<br />SUBMITTALS WHICH ARE NOT MARKED WITH EQUIPMENT TAGS OR PERFORMANCE
<br />DATA WILL BE REJECTED.
<br />12. PROVIDE PERMANENT ENGRAVED PLASTIC NAME PLATED FOR ALL EQUIPMENT
<br />INSTALLED, INDICATING THE PLAN DESIGNATION OF THE UNIT (AC -1, REF., ETC.) AND
<br />ALSO THE BUILDING AREA SERVED (CLASSROOMS 2-40 CONFERENCE ROOM, ETC.).
<br />STAMPED METAL TAPES APPLIED WITH SELF-CONTAINED ADHESIVE WILL NOT BE
<br />ACCEPTABLE.
<br />13. CONTRACTOR SHALL VERIFY ALL WORK CONDITIONS PRIOR TO COMMENCING
<br />WORK INCLUDING, BUT NOT LIMITED TO: DIMENSIONS, EQUIPMENT, STRUCTURAL
<br />ELEMENTS AND MATERIALS INDICATED AS EXISTING, AS WELL AS THE
<br />COORDINATED INSTALLATION OF ALL NEW WORK MATERIALS, EQUIPMENT, ETC.
<br />COORDINATE THE LOCATION OF ALL ROOF MOUNTED EQUIPMENT WITH THE
<br />STRUCTURAL ENGINEER
<br />14. CONTRACTOR SHALL FIELD COORDINATE AND INSTALL PACKAGED ROOFTOP
<br />EQUIPMENT TO MAINTAIN A MINIMUM OF 10'-0" CLEARANCE FROM OUTSIDE AIR
<br />INTAKE TO ALL EXHAUST OUTLETS AND (VTR) VENT THRJ ROOF, TYPICAL.
<br />MECHANICAL SYSTEMS DESIGN REFLECT EQUIPMENT SPECIFIED.
<br />15. %=TTS" ATE_
<br />WHEN EQUIPMENT SUBSTITUTIONS OCCUR AND DUCT DESIGN, DUCT DROPS, GAS
<br />INPUT AND ELECTRICAL SERVICE VARIES FROM THAT SPECIFIED, THEN IT SHALL
<br />BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR FOR ALL
<br />ADDITIONAL ENGINEERING FEES AND OTHER DISCIPLINE CHANGE ORDERS
<br />(STRUCTURAL, ELECTRICAL, ARCHITECTURAL, PLUMBING, ETC) WHEN SUBSTITUTED
<br />EQUIPMENT IS USED.
<br />16. PERFORMANCE TEST OF THE INSTALLATION OF THE VENTILATION SYSTEM FOR
<br />HEAT -PROCESSING EQUIPMENT PER CMC 51122 (AIR BALANCE REPORT)
<br />IT VERIFY THAT 16" SPACE BETWEEN THE FYER AND THE RANGES PER CMC 101.1.4.
<br />I8. PRIOR TO FINAL COMPLIANCE WITH 5013 MUST BE AVAILABLE TO THE INSPECTOR: A DRAWING
<br />(S) OF THE EXHAUST SYSTEM INSTALLATION ALONG WITH A COPY OF OPERATING INSTRUCTIONS
<br />SUBASSEMBLIES AND COMPONENTS USED IN THE EXHAUST SYSTEM, INCLUDING ELECTRICAL
<br />SCHEMATICS, SHALL BE AVAILABLE ON PREMISES.
<br />EQUIPMENT SCHEDULE
<br />GRILLE SCHEDULE
<br />DESCRIPTION
<br />SYMBOL
<br />DESORPTION
<br />DI
<br />TITUS MODEL TDC OR EQUAL, LOUVERED FACE, ALL STEEL
<br />Ell DO PRESS.
<br />CONSTRUCTION LAY -IN 24"44" T -BAR FRAME, WITH OPPOSED BLADE
<br />Q
<br />DAMPER, STANDARD WHITE FINISH.
<br />p2
<br />TITUS MODEL 6300FS OR EQUAL, DOUBLE DEFLECTION, 34" BLADE
<br />SPACING, INDIVIDUAL BLADE ADJUSTMENT, WITH OPPOSED BLADE
<br />MUA-2
<br />DAMPER PAINT READY FINISH FOR EXPOSED DUCTS AND
<br />-
<br />STANDARD WHITE FINISH FOR CEILING APPLICATIONS.
<br />RI
<br />TITUS MODEL 50F OR EQUAL, EGG -CRATE FACE, 11/2" x 1/2" x 112"
<br />2910
<br />ALUMINUM GRID, LAY -IN 24044" T -BAR FRAME, WTH OPPOSED
<br />1
<br />e
<br />BLADE DAMPER STANDARD WHITE FINISH.
<br />R2
<br />TITUS MODEL 50F OR EQUAL, EGG -CRATE FACE, 11/2" x 1/2" x 11/2"
<br />65
<br />ALUMINUM GRID, SURFACE MOUNT FRAME, WITH OPPOSED BLADE
<br />GEF
<br />DAMPER STANDARD WHITE FINISH. EI SIMILAR E KEPT FURNISH
<br />-
<br />WITHOUT OPPOSED BLADE DAMPER
<br />NOTES:
<br />COORDINATE WITH ARCHITECT FOR PAINT FINISH QUIREMENTS FOR
<br />405
<br />ALL DIFFUSERS, GRILLES, AND REGISTERS.
<br />1600
<br />BLOW PATTERN AS INDICATED ON PLAN. (SEE A").
<br />300
<br />REFER TO ARCHITECTURAL PLAN FOR EXACT DI SER, GRILLE AND
<br />-
<br />REGISTER LOCATIONS.
<br />(E) AC -2
<br />CONTRACTOR SHALL COORDINATE DIFFUSER LOCATION WITH ALL
<br />2600
<br />OTHER TRADES AND CONDITIONS.
<br />400
<br />CONTRACTOR SHALL TRANSITION DUCTWORK TO DIFFUSER, REGISTER
<br />400
<br />AND GRILLE NECK SIZES AS REQUIRED.
<br />GENERAL MECHAMOAL NOTES
<br />ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND SHALL BE EQUAL IN
<br />QUALITY, TYPE, CAPACITY EFFICIENCY AND ACCESSORIES TO THE EQUIPMENT
<br />NOTED ON THE DRAWINGS. ADJUSTMENTS TO CONSTRUCTION AND ACCESSORIES
<br />ON SUBSTITUTED EQUIPMENT MAY BE REQUIRED TO ACHIEVE THIS EQUALITY, AND
<br />SHALL BE INCLUDED AT NO EXTRA COST TO THE OWNER MAKE ANY CHANGES IN
<br />DUCTWORK, PIPING, FRAMING, ETC., AS REQUIRED TO ACCOMMODATE
<br />SUBSTITUTED EQUIPMENT.
<br />2. INSTALL ALL EQUIPMENT AND MATERIALS AND PERFORM ALL WORK IN
<br />ACCORDANCE WITH ALL APPLICABLE CODES. APPLICABLE CODES SHALL
<br />INCLUDE, BUT NOT BE LIMITED TO THE LATEST EDITIONS OF THE CALIFORNAI
<br />MECHANICAL CODE, CALIFORNIA CODE OF REGULATIONS (CCR), CALIFORNIA FIRE
<br />REGULATIONS AND TITLE 24 ENERGY EFFICIENCY STANDARDS. WHERE HEAVIER
<br />GAGES OF MATERIAL, LAR3ER SIZES OR MORE STRINGENT REQUIREMENTS THAN
<br />THE CODES ARE REQUIRED BY THE CONTRACT DOCUMENTS, SUCH INCREASED
<br />REQUIREMENTS SHALL APPLY.
<br />3. FABRICATE AND INSTALL ALL DUCTWORK IN ACCORDANCE WITH THE LATEST
<br />EDITION OF SMACNA GUIDELINES FOR DUCT CONSTRUCTION AND THE CALIFORNIA
<br />MECHANICAL CODE. ALL DUCT JOINTS INCLUDING MECHANICAL FLANGED JOINTS
<br />SHALL BE SEALED WITH SILVER TAPE, OR ARABOL AND CANVAS. SEAL THE
<br />JOINTS OF ALL DUCTS EXPOSED TO THE WEATHER WITH ARA50L AND CANVAS.
<br />PROVIDE ALL BRANCH DUCTS WITH VOLUME DAMPERS WITH LOCKING QUADRANTS
<br />LOCATED AT LEAST FIVE FEET (59 FROM THE GRILLE OR DIFFUSER SERVED.
<br />4. SUPPORTS FOR ALL PIPING AND DUCTWORK SHALL BE IN ACCORDANCE WITH
<br />SMACNA "GUIDELINES FOR SEISMIC RESTRAINT OF MECHANICAL SYSTEMS".
<br />CONTRACTOR SHAD. PROVIDE CALCULATIONS FOR ISOLATORS AND MOUNTING
<br />ACCEPTABLE TO THE REVIEWING AUTHORITY WHEN REQUIRED BY SAME.
<br />5. ALL RECTANGULAR OR ROUND RIGID DUCTS SHALL BE OF SMACNA GAGE
<br />GALVANIZED STEEL OR ALUMINUM, UNLESS OTHERWISE NOTED ON THE DRAWINGS.
<br />PROVIDE FLAT SEAM CONSTRUCTION FOR ANY DUCTS EXPOSED IN OCCUPIED
<br />SPACE. NOTE_ : ALUMA-FLEX IS�L4C��P� I�Ig�gO�p�clC
<br />=
<br />6. FL x"j DUGT13 PER1MVD AND NULL BE awfm IL, 1414 LEx G-10'1 OR
<br />EQ LN FACTORY NOQ ATED. FLD(IM DUCTS 011 NOT !RE UBW 1111100
<br />WORMED DUc"Illo C OCCUFA BECURE FLEXIDLB DUCIUIORK WTH TI1R0
<br />MIMCK MCALLY APPLIED PI.A6TIC 6TRAP6 OR ONE W7Fd"I MW CLAIV
<br />—& RM(WE DUM W114 20 D�mA� �
<br />ti 81 W.
<br />1. INSULATE ALL SUPPLY AND RETURN DUCTS WITH 2" THICK, 3/4 PCF DENSITY O -C F
<br />OR EQUAL, FIBERGLASS DUCT WRAP, TYPE IV, WITH FACTORY APPLIED FLAME
<br />RETARDANT FOIL REINFORCED KRAFT FACING. LAP ALL JOINT 4" MINIMUM, AND
<br />SECURE WITH GALVANIZED STEEL WIRE.
<br />8. LINE ALL SUPPLY AND RETURN DUCT DROPS FOR A MINIMUM OF 10' FROM THE
<br />UNIT WITH I" THICK O -C F AEROFLEX TYPE 200 OR EQUAL ACOUSTIC DUCT
<br />LINER INSTALL WITH 100% COVERAGE ADHESIVE, AND FURTHER APPLY
<br />MECHANICAL PIN FASTENERS WFERE DUCT SIDE EXCEEDS 24". DUCT DIMENSIONS
<br />ARE NET INTERNAL DIMENSION. SEAL BUTT ENDS OF EXPOSED INSULATION IN THE
<br />DUCTS WITH MANUFACTURERS RECOMMENDED SEALANT OR ADHESIVE.
<br />9• CONTROLS SHALL COMPLY WITH THE LATEST EDITION OF CEG ( JULY 2016),
<br />ALL CONTROLS AND CONTROL WIRING NOT
<br />SPECIFICALLY SHOWN BUT REQUIRED FOR A COMPLETE AND WORKABLE SYSTEM
<br />SHALL BE SUPPLIED BY THE CONTRACTOR AND INSTALLED AT NO ADDITIONAL
<br />COST TO THE OWNER
<br />10. ALL AIR SYSTEMS SHALL BE BALANCED BY A QUALIFIED MECHANICAL
<br />CONTRACTOR USING AABC, SMACNA OR NEBB PROCEDURES. AIR QUANTITIES
<br />SHALL BE BALANCED TO NOT MORE THAN 10% ABOVE OR 0% BELOW THE
<br />QUANTITIES SHOUN ON THE DRAWWjS. CONTRACTOR SHALL SUBMIT A COMPLETE
<br />AIR BALANCE REPORT INDICATING, AS A MINIMUM, THE AIR DELIVERY FOR EACH
<br />DIFFUSER THE FINAL OPERATING DATA FOR THE SYSTEMS AND THE AIR
<br />CONDITIONING UNITS.
<br />11. SUBMIT FOR APPROVAL (6) COPIES OF COMPLETE SUBMITTAL DATA ON
<br />SPECIFIED AND PROPOSED EQUIPMENT AND MATERIALS. SUBMITTALS SHALL
<br />INCLUDE EQUIPMENT SIZES, CAPACITY, MOTOR LOCATIONS, PERFORMANCE
<br />CURVES AND OTHER PERTINENT DATA EACH SUBMITTAL SHALL INCLUDE
<br />IDENTIFICATION TAGS OR SYMBOLS TO MATCH DOGS. PARTIAL SUBMITTALS OR
<br />SUBMITTALS WHICH ARE NOT MARKED WITH EQUIPMENT TAGS OR PERFORMANCE
<br />DATA WILL BE REJECTED.
<br />12. PROVIDE PERMANENT ENGRAVED PLASTIC NAME PLATED FOR ALL EQUIPMENT
<br />INSTALLED, INDICATING THE PLAN DESIGNATION OF THE UNIT (AC -1, REF., ETC.) AND
<br />ALSO THE BUILDING AREA SERVED (CLASSROOMS 2-40 CONFERENCE ROOM, ETC.).
<br />STAMPED METAL TAPES APPLIED WITH SELF-CONTAINED ADHESIVE WILL NOT BE
<br />ACCEPTABLE.
<br />13. CONTRACTOR SHALL VERIFY ALL WORK CONDITIONS PRIOR TO COMMENCING
<br />WORK INCLUDING, BUT NOT LIMITED TO: DIMENSIONS, EQUIPMENT, STRUCTURAL
<br />ELEMENTS AND MATERIALS INDICATED AS EXISTING, AS WELL AS THE
<br />COORDINATED INSTALLATION OF ALL NEW WORK MATERIALS, EQUIPMENT, ETC.
<br />COORDINATE THE LOCATION OF ALL ROOF MOUNTED EQUIPMENT WITH THE
<br />STRUCTURAL ENGINEER
<br />14. CONTRACTOR SHALL FIELD COORDINATE AND INSTALL PACKAGED ROOFTOP
<br />EQUIPMENT TO MAINTAIN A MINIMUM OF 10'-0" CLEARANCE FROM OUTSIDE AIR
<br />INTAKE TO ALL EXHAUST OUTLETS AND (VTR) VENT THRJ ROOF, TYPICAL.
<br />MECHANICAL SYSTEMS DESIGN REFLECT EQUIPMENT SPECIFIED.
<br />15. %=TTS" ATE_
<br />WHEN EQUIPMENT SUBSTITUTIONS OCCUR AND DUCT DESIGN, DUCT DROPS, GAS
<br />INPUT AND ELECTRICAL SERVICE VARIES FROM THAT SPECIFIED, THEN IT SHALL
<br />BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR FOR ALL
<br />ADDITIONAL ENGINEERING FEES AND OTHER DISCIPLINE CHANGE ORDERS
<br />(STRUCTURAL, ELECTRICAL, ARCHITECTURAL, PLUMBING, ETC) WHEN SUBSTITUTED
<br />EQUIPMENT IS USED.
<br />16. PERFORMANCE TEST OF THE INSTALLATION OF THE VENTILATION SYSTEM FOR
<br />HEAT -PROCESSING EQUIPMENT PER CMC 51122 (AIR BALANCE REPORT)
<br />IT VERIFY THAT 16" SPACE BETWEEN THE FYER AND THE RANGES PER CMC 101.1.4.
<br />I8. PRIOR TO FINAL COMPLIANCE WITH 5013 MUST BE AVAILABLE TO THE INSPECTOR: A DRAWING
<br />(S) OF THE EXHAUST SYSTEM INSTALLATION ALONG WITH A COPY OF OPERATING INSTRUCTIONS
<br />SUBASSEMBLIES AND COMPONENTS USED IN THE EXHAUST SYSTEM, INCLUDING ELECTRICAL
<br />SCHEMATICS, SHALL BE AVAILABLE ON PREMISES.
<br />EQUIPMENT SCHEDULE
<br />SYMBOL
<br />DESCRIPTION
<br />RETURN AR
<br />COOLING CAPACITIES AIRE BASED AT 105 F. AMB., 80 F. DB, 61 F. WB,
<br />MAKE-UP AR
<br />ENTERING AIR TEMPERATURE.
<br />Ell DO PRESS.
<br />HEATING CAPACITIES ARE BASED AT 30 F.
<br />Q
<br />PACKAGED ROOFTOP AIR-CONDITIONING UNIT WITH NATURAL GAS
<br />V
<br />FIRED HEATING, ELECTRIC COOLING WITH PURON REFRIGERANT,
<br />VERTICAL DISCHARGE, LOW HEAT CAPACITY. FURNISH COMPLETE WITH
<br />MUA-2
<br />ROOF CURB, BELT -DRIVE MOTORS, MANUAL OUTDOOR AIR DAMPER
<br />-
<br />PROGRAMMABLE THERMOSTAT, DISPOSABLE FILTERS IN FILTER RACK.
<br />NEW
<br />CARRIER MODEL NO.: 4814CDA05 OR EQUAL, 15b SEER, 82.0 AFUE,
<br />2910
<br />NOMINAL 4.0 TON UNIT.
<br />1
<br />e
<br />TOTAL COOLING CAPACITY: 41,100 BTUH
<br />-
<br />SENSIBLE COOLING CAPACITY: 31000 BTUH
<br />65
<br />HEATING CAPACITY: 12,000 BTUH INPUT
<br />GEF
<br />56000 BTUH OUTPUT
<br />-
<br />AIR FLOW SETTING: 1600 COM AT 05 E.S.P.
<br />-
<br />ELECTRICAL SERVICE: 208 V/3 PH/60 HZ.
<br />405
<br />COMPRESSOR: I AT 13.1 RLA, 83.0 LRA
<br />1600
<br />EVAPORATOR FAN MOTOR: I AT ID BHP, 52 FLA
<br />300
<br />CONDENSER FAN MOTOR, I AT 025 HP, 1.4 FLA
<br />-
<br />COMBUSTION FAN MOTOR: I AT AS FLA
<br />(E) AC -2
<br />MCA: 24.0
<br />2600
<br />MOCP: 30.0
<br />400
<br />UNIT WEIGHT: 590 LBS.
<br />400
<br />OUTSIDE AIR SETTING: 400 CFM
<br />4600
<br />CONTRACTOR SHALL CLEAN AND REPAIR EXISTING PACKAGED ROOF
<br />EXISTNG
<br />TOP AC UNIT BEFORE RETURNING UNIT TO SERVICE. REPAIRS SHALL
<br />3430
<br />INCLUDE REPLACEMENT OF BELTS, AND FILTER, AND UNIT
<br />y
<br />e
<br />REFRIGERANT SHALL BE RECHARGED. MODIFY OUTSIDE AIR INTAKES
<br />TO ACCOMMODATE AIR QUANTITIES SPECIFIED.
<br />TRANE MODEL NO.: YSC092 OR EQUAL, 112 EER, 81 AFUE, NOMINAL 15
<br />TON UNIT.
<br />AIR FLOW SETTING: 3000 CFM AT 05 E.S.P.
<br />ELECTRICAL SERVICE: 208 V/3 P14/60 HZ.
<br />MCA: 433
<br />MOCP: 50.0
<br />WEIGHT: 1100 LBS
<br />OUTSIDE AIR SETTING: 350 CFM
<br />CEf CE
<br />GREENHECK MODEL NO.: SP -590 OR EQUAL
<br />1
<br />AIR FLOW SETTING: 65 CFM AT 325 S.P., 100 RPM
<br />-2/
<br />ELECTRICAL SERVICE: 120 V/1 P14/60 HZ., 50 WATTS
<br />CONTROL WITH ROOM LIGHTS.
<br />WEIGHT: 10 LBS.
<br />FURNISH: BACKDRAFT DAMPER, INTERCONNECTING DUCT, INHERENT
<br />THERMAL MOTOR PROTECTION, TIME -DELAY SWITCH, ROOF CAP,
<br />SPEED CONTROLLER MOUNTED ON UNIT CASING.
<br />}
<br />HOOD EXHAUST FAN
<br />CAPTIVE AIRE SEE HOOD PLANS
<br />UA
<br />MAKE UP AIR UNIT
<br />2
<br />CAPTIVE AIRE SEE HOOD PLANS
<br />AIR BALANCE SCHEDULE
<br />UNIT TAG
<br />SUPPLY AR
<br />RETURN AR
<br />OUTS= AR
<br />MAKE-UP AR
<br />EXHAUST AR
<br />Ell DO PRESS.
<br />J
<br />Q
<br />W
<br />V
<br />Z
<br />MUA-2
<br />-
<br />-
<br />-
<br />2910
<br />-
<br />2910
<br />GEF
<br />-
<br />-
<br />-
<br />-
<br />65
<br />-65
<br />GEF
<br />-
<br />-
<br />-
<br />-
<br />65
<br />405
<br />AC -1
<br />1600
<br />1300
<br />300
<br />300
<br />-
<br />300
<br />(E) AC -2
<br />3000
<br />2600
<br />400
<br />400
<br />-
<br />400
<br />TOTAL
<br />4600
<br />3900
<br />100
<br />3610
<br />3430
<br />240
<br />I. INTERLOCK HEF-I AND MAU-1
<br />2. HOOD EXHAUST FAN SHALL CONTINUE TO OPERATE AFTER THE EXTINGUISHING SYSTEM IS
<br />ACTIVATED UNLESS SHUTDOWN IS REQUIRED AS A COMPONENT OF THE EXTINGUISHING
<br />SYSTEM. CMC 51123.
<br />3. APPLIANCES SERVED SHALL BE INTERLOCKED TO THE MECHANICAL AIR SUPPLY
<br />SYSTEM TO PREVENT MAIN BURNER OPERATION WHERE THE MECHANICAL AIR SUPPLY
<br />SYSTEM IS NOT IN OPERATION. CMC 10182.
<br />REVISIONS
<br />Q DESCRIPTION DATE
<br />AFIRE DEPARTMEN
<br />FL
<br />4m
<br />PRG.S'cyF�G
<br />No. 3/f95S
<br />`lh� OF CAI.\F�R�
<br />Date Signed: January 15, 2020
<br />a
<br />J
<br />J
<br />W
<br />W
<br />w
<br />W
<br />m
<br />SHEET TITLE
<br />MECHANICAL
<br />LEGEND AND
<br />SCHEDULES
<br />DATE OCTOBER 8, 2019
<br />DRAWN BY EH
<br />CHECKED BY BC
<br />SCALE: as noted
<br />SHEET
<br />m 1
<br />~
<br />M^
<br />,
<br />Y♦
<br />J
<br />Q
<br />W
<br />V
<br />Z
<br />W
<br />00
<br />qq
<br />Z
<br />TOM
<br />N
<br />Q
<br />SHEET TITLE
<br />MECHANICAL
<br />LEGEND AND
<br />SCHEDULES
<br />DATE OCTOBER 8, 2019
<br />DRAWN BY EH
<br />CHECKED BY BC
<br />SCALE: as noted
<br />SHEET
<br />m 1