Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> C O U N T AMENDED <br /> 9/8/2021 <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> EI Dorado Gas&Mart 1605 S EL DORADO ST, STOCKTON July 28, 2021 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 210 CCR 2715(c)Failure to provide initial training,train every 12 months, and have a trained employee present. <br /> OBSERVATION: The designated operator employee training for facility employees has not performed. <br /> REGULATION GUIDANCE: The designated operator shall train facility employees in the proper operation and <br /> maintenance of the UST system at least once every 12 months. The training shall be conducted before the <br /> individual performs the duties of a facility employees.The training shall include, but is not limited to: <br /> 1. Operation of the UST system in a manner consistent with the facility's best management practices <br /> 2. Employee's role with regard to monitoring equipment as specified in the facility's monitoring plan <br /> 3. Employee's role with regard to spills and overfills as specified in the facility's response plan <br /> 4. Name of the contact person(s)for emergencies and monitoring equipment alarms <br /> Initial training shall also include a site-specific practical demonstration that provides both sharing information and <br /> evaluating knowledge for responding to emergencies, leak detection, monitoring alarms, spills and overfills. At least <br /> one of the facility employees present during operating hours shall have current training. <br /> CORRECTIVE ACTION: Ensure that employees have been trained by the designated operator, maintain the list on <br /> site, and submit a copy of the training records to the EHD. <br /> This is a Class II violation. <br /> 308 CCR 2632(c), 2634(d), 2636(f) Failure of the leak detection equipment to have an audible and visual alarm. <br /> The 87 float and chain in the 3/4 UDC failed to stop the flow of product at the dispenser when tested. <br /> REGULATION GUIDANCE:All monitoring equipment shall be maintained to activate an audible and visual alarm or <br /> stop the flow of product at the dispenser when it detects a leak. <br /> CORRECTIVE ACTION: The service technician adjusted the float and chain and verified functionality. <br /> This is a Class II violation. <br /> 309 CCR 2666(b)(2), 2636(f)(1) Failure to have continuous monitoring that activates audible-visual alarm or stops flow at <br /> dispenser. <br /> OBSERVATIONS: The UDCs failed to have monitoring equipment that activates an audible and visual alarm or <br /> stop the flow of product at the dispenser when it detects a leak. On 07/21/2021, per service technician David <br /> Winker,the monitoring system certification testing could not be performed because the UDCs did not have sensors <br /> and the floats did not have chains connected to the Schrader valve. <br /> REGULATION GUIDANCE:All monitoring equipment shall be maintained to activate an audible and visual alarm or <br /> stop the flow of product at the dispenser when it detects a leak. <br /> CORRECTIVE ACTION: The floats and chains were tested and passed during the inspection on 07/28/2021. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> An inspection checklist was provided to the facility operator at the time of inspection. A full inspection report <br /> FA0006185 PR0504388 SC333 07/28/2021 <br /> EHD 23-01 Rev.9/16/2020 Page 8 of 9 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />