Laserfiche WebLink
DYNAMIC BACK PRESSURE TEST DATA (BLOCKAGE) TECHNICIAN: FELIX RAMIREZ <br /> Cert#0099 <br /> Site: EL DORADO GAS MART Date: 05-27-20 Time: 815 <br /> Nozz/Fuel 20 CFH 60 CFH 80 CFH PASS/FAIL Nozz/Fuel 20 CFH 60 CFH 80 CFH PASS/FAIL <br /> Grade (.15"Water) (.35" Water) (.62" Water) Grade (.15" Water) (.35" Water) (.62" Water) <br /> 1 ALL .24 .41 PASS 2 ALL .23 .32 PASS <br /> 3 ALL .22 .38 PASS 4 ALL .22 .33 PASS <br /> 5 ALL .24 .36 PASS 6 ALL .26 .42 PASS <br /> LIQUID REMOVAL CHECK **See Long Form Test Report for Wet Failure Testing Blockage Tester Integrity: <br /> D=Dry 1 "w.c. 5 minutes PASS <br /> [-]DRY ❑DRY ❑DRY ❑DRY [-]DRY ❑DRY ❑DRY [-]DRY ❑DRY <br /> M1 ml ml ml ml ml ml ml ml <br /> ❑DRY [:]DRY ❑DRY []DRY ❑DRY [:]DRY ❑DRY ❑DRY ❑DRY <br /> M1 ml ml ml ml ml ml ml ml <br /> ❑DRY [:]DRY ❑DRY ❑DRY I ❑DRY ❑DRY ❑DRY ❑DRY ❑DRY <br /> M1 ml ml ml ml ml ml ml ml <br /> []DRY ❑DRY ❑DRY ❑DRY [-]DRY ❑DRY ❑DRY [-]DRY ❑DRY <br /> M1 ml ml ml ml ml ml ml ml <br /> ❑ Job Complete Repairs Done to Pass Test: <br /> ❑ I Not Complete Repairs Still Needed: <br /> Parts: I <br /> None Drop Tube rings Fill Adaptor Gaskets Hoses Whip Hose <br /> Nozzles I Breakaways PV Valves Others: <br />