Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 9. COMMENTS <br /> OC Tank=Owens Corning Tank. Smith FRP=Smith Fiberglass Reinforced Plastic. PS=Piping <br /> Sump. Unknown FGC=Unknown Figerglass Construction. <br /> Note: Piping Sump will not maintain test level. I reset the Level Change Indicator several times to <br /> confirm a consistent loss. Found a large gap on the Vent Piping Pentration/Piping Sump Wall <br /> interface. Visual sign of small bubbles in the test fluid, at the Product Piping Piping Penetration. <br /> The two Electrical Penetrations, are showing signs of cracks. Recommend a repair contractor be <br /> consulted. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 5 of 5 <br />