Laserfiche WebLink
RP ASSOCIATES, INC. PROJECT: 8288 S EI Dorado St. French Camp, CA <br /> CONSULTING ENGINEERS SHEET N0. OF JOB NO. 21-16 <br /> 140 MAYHEW WAY, SUITE 507 <br /> PLEASANT HILL, CA 94523 CALCULATION BY: R. Patel DATE 04/30/2021 <br /> = (4,650 + 950) X 0.144 <br /> = 806 lbs. <br /> STABILITY <br /> MOT = 806 X (4/2 + 0.33) <br /> = 1,881 lb-ft. <br /> MR (4,650 + 950) X 3.25 / 2 <br /> = 9,100 Ib-ft. <br /> MR > MOT — No overturning. <br /> ANCHORAGE <br /> Concrete footing fc' = 2,500 psi <br /> Existing Concrete Floor— 6" thick <br /> V = 806/4 <br /> = 202 lbs. each corner. <br /> Provide 4 X 4 X 1/4 Angle with 1 - '/2" dia. Simpson Strong Bolt — 2SS <br /> Expansion Anchors with 3" Embedment. <br /> See Calculation Appendix C for analysis and design. <br /> FOOTING <br /> Allowable Soil Pressure = 1,500 psf <br /> p = 5,600 / (4.25 X 1.33) <br /> = 988 psf. <br />