Laserfiche WebLink
PA- 1900284 (SA) , Referral , S00013872 Page 2 of 2 <br /> 4010 E . Fremont St , Stockton January 28 , 2021 <br /> c) Reportable quantities of hazardous materials - reportable quantities are 55 gallons or more of <br /> liquids , 500 pounds for solids , or 200 cubic feet for compressed gases , with some exceptions . <br /> Carbon dioxide is a regulated substance and is required to be reported as a hazardous material <br /> if storing 1 , 200 cubic feet ( 137 pounds ) or more onsite in San Joaquin County — Hazardous <br /> Materials Business Plan Program ( HSC Sections 25508 & 25500 et sec . ) <br /> d ) Any amount of hazardous material stored in an Underground Storage Tank — Underground <br /> Storage Tank Program ( HSC Sections 25286 & 25280 et sec . ) <br /> i ) If an underground storage tank ( UST) system will be installed , a permit is required to be <br /> submitted to , and approved by , the San Joaquin County Environmental Health Department <br /> ( EHD ) before any UST installation work can begin . <br /> ii ) Additionally , an EHD UST permit to operate is required once the approved UST system is <br /> installed . <br /> e) Storage of at least 1 , 320 gallons of petroleum aboveground or any amount of petroleum stored <br /> below grade in a vault — Aboveground Petroleum Storage Program ( HSC Sections 25270 . 6 & <br /> 25270 et sec . ) <br /> i ) Spill Prevention , Countermeasures and Control ( SPCC ) Plan requirement <br /> f) Threshold quantities of regulated substances stored onsite - California Accidental Release <br /> Prevention ( CaIARP ) Program (Title 19 , Section 2735 . 4 & HSC Section 25531 et sec . ) <br /> i ) Risk Management Plan requirement for covered processes <br />