The following is an itemized list of underground storage tank violations that have not <br /> been addressed for ARCO 06080 as of September 02, 2021. <br /> Open violations from January 19, 2021 inspection <br /> Violation #307 -Failure to keep water out of the secondary containment system (post-Jul 2003). <br /> OBSERVATION Liquid was found in the 87 STP sump,91 STP sump, diesel STP sump, diesel fill sump and vent <br /> transition sump. <br /> REGULATION GUIDANCE: Secondary containment shall be constructed to prevent any liquid intrusion into the <br /> system by precipitation, infiltration, or surface runoff. <br /> CORRECTIVE ACTION: The service technician removed approximately 2 cups of liquid from the 87 STP sump,91 <br /> STP sump, diesel STP sump, diesel fill sump and vent transition sump and returned the sensor to its proper <br /> location. Immediately contact a properly licensed, trained, and certified contractor to address the liquid intrusion into <br /> the the 87 STP sump,91 STP sump, diesel STP sump, diesel fill sump and vent transition sump under permit and <br /> inspection of the EHD. <br /> This violation was corrected ❑ This violation will be corrected by (date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation:Gettler-Ryan responded to the above violation on 2/1/21. <br /> For their response, they checked all the sumps for liquid and brine removed water they found, and all sumps were <br /> cleared that day. Gettler-Ryan returned on 2/9/21 to replace damaged sump lid gaskets and fill/vapor lids. <br /> Please see attached work orders further detailing work done onsite in response to this violation. <br /> Page 1 of 1 <br />