Laserfiche WebLink
Underground Storage Tank <br /> Overfill Prevention Equipment Inspection Report <br /> 6. OVERFILL PREVENTION EQUIPMENT DETAILS <br /> Tani{ ID (one OPE per column) T1 87 TZ 91 T3 Diesel <br /> Are both vent and tank riser piping VYes V( Yes �/j Yes Yes <br /> secondarily contained? No No No No <br /> OPE Model Veeder Root Veeder Root Veeder Root <br /> What is the OPE response when activated? Shut off Shut off Shut off Shut off <br /> (Check all that apply.) Flow Flow Flow Flow <br /> estricts estricts estricts Restricts <br /> Flow Flow Flow Flow <br /> Z/ Audible 0/ Audible r/ Audible Audible <br /> Alarm Alarm Alarm Alarm <br /> Visual �v/ Visual Visual Visual <br /> Alarm Alarm Alarm Alarm <br /> Are flow restrictors installed on vent piping Yes* Yes* Yes* Yes* <br /> that may interfere with the OPE operation? LNo No �/ No No <br /> At what level in the tank is the OPE set to <br /> activate? Inches from bottom of tank 100" 99 3/8" 99 I/e" <br /> What is the percent capacity of the tank at <br /> 90$ 90% 90% <br /> which the OPE activates? <br /> Is the OPE in proper operating condition to �/ Yes �/ Yes �/ Yes Yes <br /> respond when the stored substance No No No No <br /> reaches the designated regulatory level?. <br /> 7. SUMMARY OF TESTING RESULTS <br /> OPE Inspection Results / Pass 1/ Pass Pass Pass <br /> Fail Fail Fail Fail <br /> $. COMMENTS <br /> Describe all results marked "Fail"and each proposed remedy. <br /> * Mark here if: <br /> Flow restrictors interfere with overfill prevention and equipment repairs required. <br /> Additional copies of this page may be attached. <br /> Attach tank chart(s), measurements, calculations, and In-Tank Setup reports) <br /> Page 2 of 2 <br />