Laserfiche WebLink
The following is an itemized list of hazardous waste violations that have not been <br /> addressed for QUEST INDUSTRIES LLC as of January 11, 2021. <br /> Open violations from November 04, 2020 inspection <br /> Violation#502-Failed to comply with new hazardous waste tank system assessment requirements. <br /> OBSERVATION:The facility treats paint waste in a 70 gallon heated tank. The treated paint waste was sampled by <br /> the EHD on 11/4/2020 and was found to be toxic hazardous waste for Zinc content. Samples 6 and 7 were found to <br /> be 120,000 and 51,000 mg/kg Zinc, respectively. The facility did not have a hazardous waste tank assessment for <br /> the treatment tank. <br /> REGULATION GUIDANCE: <br /> Title 22 California Code of Regulations section 66260.10 <br /> "Tank"means a stationary device,designed to contain an accumulation of hazardous waste which is constructed <br /> primarily of nonearthen materials(e.g.,wood, concrete, steel,plastic)which provide structural support. <br /> Title 22 California Code of Regulations 66265.192(a) <br /> Owners or operators of new tank systems or components shall ensure that the foundation,structural support, <br /> seams,connections, and pressure controls(if applicable)are adequately designed and that the tank system has <br /> sufficient structural strength, compatibility with the waste(s)to be transferred, stored or treated, and corrosion <br /> protection so that it will not collapse, rupture, or fail.The owner or operator shall obtain a written assessment <br /> reviewed and certified by an independent,qualified, professional engineer, registered in California in accordance <br /> with section 66270.11(d)attesting that the system has sufficient structural integrity, is acceptable for the <br /> transferring,storing and treating of hazardous waste, and that the tanks and containment system are suitably <br /> designed to achieve the requirements of this article.This assessment shall be obtained prior to placing the tank <br /> system in service, and shall be kept on file at the facility.This assessment shall also include, at a minimum,the <br /> following information: <br /> (1)design standard(s)according to which the tank(s)and ancillary equipment are or will be constructed; <br /> (2)hazardous characteristics of the waste(s)to be handled; <br /> (3)for new tank systems or components in which the external shell of a metal tank or any external metal component <br /> of the tank system is or will be in contact with the soil or with water, a determination by a corrosion expert of: <br /> (A)factors affecting the potential for corrosion, including but not limited to: <br /> 1.soil moisture content; <br /> 2.soil pH; <br /> 3.soil sulfides level; <br /> 4.soil resistivity; <br /> 5.structure to soil potential; <br /> 6. influence of nearby underground metal structures(e.g., piping); <br /> 7.stray electric current; and, <br /> 8.existing corrosion-protection measures(e.g.,coating,cathodic protection), and <br /> (B)the type and degree of external corrosion protection that are needed to ensure the integrity of the tank system <br /> during the use of the tank system or component, consisting of one or more of the following: <br /> 1.corrosion-resistant materials of construction such as special alloys or fiberglass-reinforced plastic; <br /> 2. corrosion-resistant coating(such as epoxy or fiberglass)with cathodic protection(e.g., impressed current or <br /> sacrificial anodes); and <br /> 3.electrical isolation devices such as insulating joints and flanges; <br /> (4)for underground tank system components that are likely to be affected by vehicular traffic, a determination of <br /> design or operational measures that will protect the tank system against potential damage; and <br /> (5)design considerations to ensure that: <br /> (A)tank foundations will maintain the load of a full tank; <br /> (B)tank systems will be anchored to prevent flotation or dislodgement where the tank system is placed in a <br /> saturated zone, or is located within a seismic fault zone;and <br /> (C)tank systems will withstand the effects of frost heave. <br /> Title 22 California Code of Regulations section 66270.11 <br /> (d)Certification. I certify under penalty of law that this document and all attachments were prepared under my <br /> direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and <br /> evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those <br /> persons directly responsible for gathering the information,the information submitted is,to be the best of my <br /> Page 13 of 22 <br /> i <br />