PREVENTATIVE MAINTENANCE cations. Performance Requirement; Leak rate to be less <br /> Annually, Inspect the flapper in the 71 SO to see that it is than or equal to 0. 17 CFH@2.0" W.C. <br /> open by looking down the drop tube opening. Test the <br /> 71 SO drop tube seals with CARE procedure TP-201 A D. Torque Specification <br /> If the drop tube seal passes testing, no further mainte- Taptite Screws, # 10-24 thread cutting, 20 in-Ibs mini - <br /> nance is required . If the drop tube fails testing, replace mum to 35 in-lbs maximum. Testable Models Only: <br /> the drop tube seal with OPW PIN: H11931 M for 4" Socket Adaptor, 1 /4" NPT, 3.5 ft-lbs (42 in-lbs) minimum <br /> Tubes. Retest the 7150 drop tube with GARB proce- to 5.0 ft lbs (60 in-Ibs) maximum, <br /> dare TP-201 .1 D, The lower tube o-ring seal OPW P/N: Wmmmmmm <br /> H14840M can also be replaced. If this does not correct IMPORTANT: Leave these installation instructions <br /> the leak the 71 SO needs to be replaced, and maintenance procedures with the station opera - <br /> tor, <br /> FOR TESTABLE MODELS ONLY: The socket adaptor <br /> can be removed and poppet and float movement and <br /> function Inspected without removing the valve. See <br /> Page 17 for full testing details. If replacement parts are <br /> needed fortestable models the following items are <br /> available: OPW P/N 206741 Testable Inlet Tube S/A, <br /> 206740 Socket Adaptor and Cable Assembly, and 61 SOK <br /> I-m0Q01 Float it, <br /> CAUTION: Do not insert any foreign object into drop <br /> tube if flapper is in the dosed position. For exam- <br /> ple, a tank level measuring stick. This will damage <br /> the valve and void the Warranty. ALWAYS check <br /> flapper location before "sticking" the tank. If flap- <br /> per Is in the closed position, the tank is either over- <br /> filled and you need to wait until the liquid level goes <br /> down orthe 71SO is damaged and needs to be re- <br /> placed* vfvwsa%–�- <br /> 71 SO Performance Specifications <br /> This Overfill Prevention Valve has been manufactured <br /> and tested to, and met, the following California speclfi- <br /> 18 <br />