PREVENTATIVE MAINTENANCE cations. Performance Requirement. Leak rate to be less <br /> Annually,inspect the flapper in the 7150 to see that it is than or equal to 0.17 CFH@2.W W.C. <br /> open by looking down the drop tube opening. Test the <br /> 71 SO drop tube seals with CARB procedure TP-201.1 D. Torque Specificatior, <br /> If the drop tube seal passes testing, no further mainte- Taptite Screws, #10-24 thread cutting,70 in-lbs mini- <br /> nance is required. If the drop tube fails testing,replace mum to 35 in-lbs maximum. Testable Models Only- <br /> the drop tube seal with OPW P/N:H11931 M for 4' Socket Adaptor, 114"NPT,3.5 ft-lbs 02 in-lbs} minimum <br /> Tubes. Re-test the 7150 drop tube with CARB proce- to S.4 ft-lbs(60 in-lbs)maximum. <br /> duce TP-203.1 D. The lower tube o-ring seal OPW P/N: <br /> H14840M can also be replaced. if this does not correct IMPORTANT: Leave these installation instructions <br /> the leak the 7150 needs to be replaced. and maintenance procedures with the station opera- <br /> FOR TESTABLE MODELS€ NLY': The socket adaptor tor, <br /> Can be removed and poppet and float movement and <br /> function inspected without removing the valve. See <br /> Page 17 forfull testing details. If replacement parts are <br /> needed for testable models the following items are <br /> available: OPW PIN 206741 Testable Inlet Tube SJA, <br /> 206740 Socket Adaptor and Cable Assembly,and 61 SOK <br /> -0lot Kit. <br /> CAUTION: Do not insert any foreign object into drop <br /> tube if flapper is in the closed position. For exam- <br /> ple,a tank level measuring stick. This will damage <br /> the valve and void the Warranty. ALWAYS check <br /> flapper location before"sticking"the tank. If flap- <br /> per is in the closed position,the tank is either over- <br /> filled and you need to wait until the liquid level goes <br /> down or the 71 SO is damaged and needs to be re- <br /> 121ace 1. <br /> 71 SO Performance Specifications <br /> This overfill Prevention Valve has been manufactured <br /> and tested to,and met,the following California specifi- <br /> 18 <br />