Laserfiche WebLink
UNDERGROUND STORAGE TANK <br /> OVERFILL PREVENTION EQUIPMENT INSPECTION REPORT FORM (Pane t of1 ) <br /> Type of Action ❑ Installation inspection El Repair inspection ® 30 Month Inspoction <br /> I • FACILITY INFORMATION <br /> CERS ID 10180541 Date of Overfill Prevention Equipment Inspocdlon <br /> 1011 /2018 <br /> Business Namo (Same as Facility Nemo or DBA-Doing Business As) <br /> Joes Travel Plaza <br /> Business Site Address City ZiP Code <br /> 15600 S Harlan Rd Lathrop 95330 <br /> 11. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION <br /> Name of UST Service Technician Performing the Inspection (Print as shown on the ICC Certification.) Phone it <br /> David Winkler 209 744-0112 <br /> Contractor i Tank Tester License it ICC Certification # ICC Certification Expiration Date <br /> 08- 1739 Ex . 3/31 /2020 8883059- UT 1 /29/2020 <br /> Overfill Prevention Equipment inspection Training and Certifications (list applicable certifications.) <br /> FF- EBW , PhikTite & EVR Phase 1 1009853708 Ex 11 - 16- 18 OPW 104-633 Ex 3- 14-2020 <br /> Emco #3207 Ex . 09-21 -2020 VR: 834975 ATG : 2/8/20 <br /> Ill . OVERFILL PREVENTION EQUIPMENT INSPECTION INFORMATION <br /> inspection Method 0 Manufacturer Guidelines (Specify): <br /> Used : Removed Drop Tubes <br /> ❑ Industry Code or Engineering Standard (Specify): <br /> ❑ Engineered Method (Specify): <br /> Attach the inspection procedures and all documentation required to determine the results. # of Attached Pages 5 <br /> TANK ID : (By tank number, stored product, etc.) 87 W 87 E 91 DSL <br /> What is the tank inside diameter? (Inches) 114 95 114 114 <br /> Is the fill piping secondarily contained? ❑ Yes R No ❑ Yes 9 No ❑ Yes 0 No ❑ Yes 21 No <br /> Is the vent piping secondarily contained? 0 Yes ❑ No [E Yes ❑ No B Yes ❑ No [R Yes ❑ No <br /> Overfill Prevention Equipment Manufacturer(s) oPw OPW OPW OPW <br /> 61 - SO 61 - SO 61 - SO 61 - SO <br /> What Is the overfill prevention equipment response ❑ Shuts Off Flow ❑ Shuts Off Flow ❑ Shuts Off Flow ❑ Shuts Off Flow <br /> when activated? ❑x Restricts Flow El Restricts Flow ❑x Restricts Flow 91 Restricts Flow <br /> (Check all that apply.) <br /> ❑ AN Alarm ❑ AN Alarm ❑ AN Alarm ❑ AN Alarm <br /> Are flow restrictors installed on vent piping? ❑ Yes ❑x No ❑ Yes B No ❑ Yes iE No ❑ Yes 9 No <br /> At what level in the tank is the overfill prevention set <br /> to activate? (inches from bottom of tank.) 99 . 5 85 10621 /4 97 1 /2 <br /> What is the percent capacity of the tank at which the 92 94 94 91 <br /> overfill prevention equipment activates? <br /> Is the overfill prevention in proper operating condition ❑x Yes I] Yes 0 Yes 0 Yes <br /> to respond when the substance reaches the <br /> appropriate level? ❑ No (Specify in V.) ❑ No (Specify in V.) ❑ No (Specify in V,) ❑ No (Specifyin V.) <br /> IV. SUMMARY OF INSPECTION RESULTS <br /> Overfill Prevention Inspection Results Q Pass ❑ Fail ❑x Pass ❑ Fail ❑x Pass ❑ Fail (>] Pass ❑ Fail <br /> V. COMMENTS <br /> Any items marked "Fail' must be explained in this section. Any additional comments may also be provided here, <br /> VI. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS INSPECTION <br /> I hereby certify that the overfill prevention equipment was inspected in accordance with California Code of Regulations, Title 23, <br /> Division 3, Chapter 16, Section 2637.2 and all the information contained herein is accurate. <br /> UST Service Technician Signature <br /> if the facility has more components than this form accommodates, additional copies of this page maybe attached. <br /> CERS = Ca6(omia Environmental Reporting System, ID = Identification, UST = Underground Storage Tank, ICC = International Code Council, AN = Audible and Visual <br />