Laserfiche WebLink
LINE & LEAK DETECTOR TEST REPORT <br /> SITE: RIPON LOVES <br /> Identify Time Log of Test Procedures VOLUME REMARKS <br /> Each Line (Military) Ambient Temperature psi READING NET <br /> Weather, Etc. BEFORE AFTER BEFORE AFTER CHANGE Conclusions, Repairs, Comments <br /> 87 1130 PRE TEST 60 <br /> 1145 BEGIN TEST 50 .0250 <br /> 1200 51 50 .0250 .0255 .0005 <br /> 1215 50 50 .0260 .0260 .0000 .0005 <br /> 1230 50 0 .0210 .0950 .730 <br /> 91 1130 PRE TEST 60 <br /> 1145 BEGIN TEST 50 .0200 <br /> 1200 51 50 .0255 .0260 .0005 <br /> 1215 50 50 .0260 .0260 .0000 .0005 <br /> 1231 BLEED BACK 50 0 .0100 .0720 .0620 <br /> DIESEL 930 PRE TEST 60 <br /> 945 BGEIN TEST 50 .0500 <br /> 1000 51 50 .0500 .0505 .0005 <br /> 1015 51 50 .0505 .0510 .0005 .0010 <br /> 1020 BLEED BACK 50 0 .0100 .0950 .0850 <br /> Page 2 of 2 <br />