Laserfiche WebLink
SP001 —Formal External Inspection <br /> Customer Name:King Island Marina Inspection Date: 11/5/2020&11/24/2020 <br /> Contact: Bagley Enterprises/Charles Spurlock(site owner) <br /> Site Address: 11530 W. Eight Mile Road.Stockton,CA <br /> Phone#:209-470-8187 <br /> Tank ID(if any): <br /> Tank Contents:Regular and Premium Gasoline <br /> Gross Capacity: 10,000 gallons(4,000&6,000 gallon split tank) <br /> Year Installed: 1999 <br /> Tank mfg:Joor MFG. <br /> Tank Model: UL 2085 Fireguard Lightweight Tank <br /> Tank Inspector:Jon Lorente-STI ID:AST-2069 <br /> Review Prior Formal and Periodic Inspections: No Date: Internal / External <br /> Copy of prior inspections available for review? No <br /> Repair alteration date? No <br /> Records of Functionality Testing of Alarms and Equipment?No <br /> Prior Annual Inspections Available for Review: No <br /> Prior Monthly Inspections Available for Review:Yes/Adequate: No <br /> Operating Inspection Frequency:Annually 4onthl eekly Daily <br /> Leak Test or other Inspection Data Available for Review? No If Yes,Date: <br /> Nameplate Date Available/Recorded: No(Contact STI with tank serial#to confirm UL spec.). <br /> Industry Standard(Fabrication&Nameplate Data) <br /> UL 142 <L 2085 L 2080 API 650 API 12F Other Not det. Unknown <br /> Tank Dimensions: <br /> Rectangular Tank: L: W: H: <br /> Cylindrical Tanks: L:_28'6" Diameter:-7'11" orizonta Vertical? <br /> Tank Shell Thickness:_1/4"tank shell/5/16" Bulkheads <br /> Determination Method ank Documentatio /placards/labels/tank manufacture UL Standar /UTT. <br /> Tank contents confirmed with tank standard:Yes <br /> AST observed to be a repurposed UST: No <br /> Is Tank inside Building or Covered: No <br /> Overall Tank System Condition: Good Fai Poor Adequate? Yes©o (if No,explain):Repair coating failures. <br /> Primary Tank Material: Steel iberglass Other Thickness: Basis: UT Spec <br /> Secondary Containment Material: Steel Fiberglass Concrete None <br /> Tank Corrosion Protectio • Paint poxy Coating Cath.Prot. Other Coating None Adequate?Ye No <br /> Coating Failure on Secondary Tank Shel *Yes o(If Yes,Consider UTT). <br /> *Double-wall AST's do not require UTT readings for the primary tank. I <br /> f Corrosion is evident on the outside <br /> surface of the secondary tank, UTT readings are required. <br /> Tank Heads: ood air Poor-Coating Failure?NO Adequate?Yes <br /> Tank Shell: Good Fairoor Coating Failure?Yes Adequate?No <br /> Tank Chime: Good Fair Poor– N/A <br /> Cathodic Protection System:N/A <br /> 1 <br />