Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for Harney Lane 76 as of October 04, 2021 . <br /> Open violations from August 18 , 2021 inspection <br /> Violation #305 - Failed to maintain secondary containment (e .g . failure of secondary containment testing ) . <br /> OBSERVATION Blue-green brine was found in the 87 and diesel turbine pump sump and 87 , 91 , and D fill sumps . <br /> REGULATION GUIDANCE: Secondary containment shall be impervious to the liquid and vapor of the substance <br /> contained and constructed to prevent structural weakening as a result of contact with any hazardous substances <br /> released from the primary containment. <br /> CORRECTIVE ACTION : Per technician , Rhome Desbiens , approximately a total of 1 . 5 gallons of brine was pumped <br /> out of the sumps . Brine was still observed in the 87 and 91 fill sumps after the technician stated he had removed the <br /> brine . Immediately contact a properly licensed , trained , and certified contractor to make repairs to the UST system <br /> under permit and inspection of the EHD . <br /> ❑ This violation was corrected ❑ This violation will be corrected by (date) : <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation : <br /> Page 7 of 7 <br />