Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br />been addressed for Harney Lane 76 as of December 06, 2021. <br />Open violations from August 18, 2021 inspection <br />Violation #305 - Failed to maintain secondary containment (e.g. failure of secondary containment testing). <br />OBSERVATION: Blue-green brine was found in the 87 and diesel turbine pump sump and 87, 91, and D fill sumps. <br />REGULATION GUIDANCE: Secondary containment shall be impervious to the liquid and vapor of the substance <br />contained and constructed to prevent structural weakening as a result of contact with any hazardous substances <br />released from the primary containment. <br />CORRECTIVE ACTION: Per technician, Rhome Desbiens, approximately a total of 1.5 gallons of brine was pumped <br />out of the sumps. Brine was still observed in the 87 and 91 fill sumps after the technician stated he had removed the <br />brine. Immediately contact a properly licensed, trained, and certified contractor to make repairs to the UST system <br />under permit and inspection of the EHD. <br />❑ This violation was corrected ❑ This violation will be corrected by (date): <br />❑ Supporting documents included <br />Describe actions taken or will be taken to correct violation: <br />Page 7 of 7 <br />