Laserfiche WebLink
SANJOAQUIN <br />COUNTY— <br />Environmental Health Department <br />AMENDED <br />5/27/2021 <br />Underground Storage Tank Program Inspection Report <br />Facility Name: <br />Facility Address: <br />Date: <br />GRANT LINE SHELL* <br />2375 W GRANT LINE RD, TRACY <br />May 26, 2021 <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />Item # <br />Remarks <br />310 <br />CCR 2636(f)(4) Failure to meet monitoring requirements in lieu of being tightness tested every 12 months. <br />OBSERVATION: The 87 tank (end tank closest to the store) does not shut -down the pump when a leak is detected <br />and is not fail safe and does not meet the requirements for annual line tightness testing exemption. <br />REGULATION GUIDANCE: All pressurized piping with secondary containment shall be pressure tested at least <br />once every 12 months at a minimum release detection of 0.1 gallons per hour at 150 percent of the normal <br />operating pressure. Continuous monitoring systems that are fail safe and shut down the pump when a leak is <br />detected, or optionally stop the flow of product at the dispenser if the leak is in the under dispenser containment <br />(UDC), shall satisfy the requirement for annual line tightness testing. <br />CORRECTIVE ACTION: Immediately schedule an annual line tightness test and provide 48 hours notification to the <br />EHD. <br />This is a Class II violation. <br />316 <br />CCR 2636, 2643(c)(1), 2666(f) Failure to install a line leak detector. <br />OBSERVATION: The pressurized piping on the 87 tank closest to the store is not equipped with an automatic line <br />leak detector. <br />REGULATION GUIDANCE: Automatic line leak detectors are required to be equipped on underground pressurized <br />piping systems that carry a hazardous substance. <br />CORRECTIVE ACTION: Correct immediately by having a properly licensed, trained, and certified contractor install a <br />leak detector (LG 113-x listed, if applicable) and obtain a permit within one business day from the EHD. If the leak <br />detector can't be installed immediately, there is a possibility that the 87 tank (closest to the store) UST system may <br />be red tagged to prevent fuel inputs. <br />This is a Class I violation. <br />FA0003772 PR0232469 SCO01 05/26/2021 <br />EHD 23-01 Rev. 9/16/2020 Page 10 of 12 Underground Storage Tank Program OIR <br />1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />