2. LIQUID CONDENSATE TRAP PHASE II EVR COMPONENTS <br /> Exhibit 1 of VR 201 and VR 202 lists components required for a Phase II EVR System with a <br /> Liquid Condensate Trap. Existing Liquid Condensate Traps may already have some of these <br /> components installed. Some of these required components are (reference all Figures): <br /> Riser Adaptor - This riser adaptor is to be installed on all risers that are connect- <br /> INCON Model TSP-K2A ed to the Liquid Condensate Trap, except for the Liquid Conden- <br /> sate Trap suction tube riser. <br /> In-Line Filter - The purpose of the in-line filter is to trap debris and rust particles <br /> Swagelok B-4F2-140 or that are traveling inside the suction line to prevent them from <br /> SS-4F2-140 (or equivalent) blocking the syphon jet valve at the turbine pump. This in-line <br /> filter is installed at the syphon inlet of the turbine pump. <br /> Stainless Steel Wired Braided Connects the suction tube to the turbine pump. <br /> Hose or 1/4" Copper Tubing <br /> (rated for use with gasoline)_ <br /> Aluminum or Stainless Steel This screen can be purchased from almost any hardware <br /> Insect Screen with Stainless store. The specifications are: 18 X 14 mesh for aluminum <br /> Steel Hose Clamp insect screen and 18 X 18 mesh for stainless steel insect <br /> screen. A small section of this screen material is installed <br /> over the end of the suction tube inside the Liquid Conden- <br /> sate Trap and secured with a SS hose clamp. <br /> Liquid Sensor Connection Many sites already have existing liquid sensors installed <br /> to the UST Monitoring System inside the Liquid Condensate Trap. If a liquid sensor does <br /> not exist inside the Liquid Condensate Trap then one must <br /> be installed. <br /> Any Liquid sensor installed inside the Liquid Condensate <br /> Trap must meet the following minimal requirements: <br /> • Provides a visual and audible alarm in case of failure of <br /> the evacuation system; <br /> • The audible and visual alarm monitoring system must <br /> be installed at a location that is most likely to be heard <br /> by the station attendant during normal station operation; <br /> • Set the liquid sensor to the height shown in Figure 5. <br /> Various Pipe Fittings For adapting the suction line, as required, and to add a <br /> in '/4" and 2" Sizes fuel entry point with a plug or cap to the Liquid Condensate <br /> Trap riser. <br /> Optional Equipment: <br /> Secondary Syphon Kit -- For use when two syphon primers are required for one Sub- <br /> Franklin Fueling Systems mersible Turbine Pump (STP). One to syphon the Liquid <br /> Part Number 402507930 Condensate Trap and one for siphoning two or more tanks <br /> of like product grade. <br /> 9-2 <br /> CARR Approved IN 9-Liquid Condensate Trap-EXECUtiVe Orders VR-201 and VR-202 <br />