TLS RF Installation Wiring the TLS RF <br /> O I I n <br /> I_I_ <br /> LI <br /> ❑ AC ® �� O PROBES—C <br /> INPUT 0 0 PROBE]—C• , <br /> © U <br /> PROBE6—C• �^J <br /> PROBES—r• <br /> O PROBE4—L <br /> aaaaaaaa RS-485 <br /> PROBE3—C• I <br /> + r <br /> I]G PROBE2—L• <br /> 0 15V <br /> PROBE 1—C• <br /> � a <br /> 15V <br /> ® ��n ❑flEPEA-ER <br /> © 9SCC o ❑❑ <br /> 964-11.eps <br /> Figure 9. Power Connections To A Daisy Chained TLS RFs <br /> LEGEND FOR • <br /> 1. POWER WIRING NOTES: 3. Protective earthing conductor(green and yellow).Attach <br /> •Barrier ground must be#12 AWG or larger diameter. #12AWG barrier ground wire to ground lug.Ground must be <br /> •Check to be sure that the electrical resistance-between the the same as the supply and less than 1.0 ohms to ground. <br /> unit ground lug and a known good earth ground is less than 1 4. Attach chassis ground wire(#14 AWG)to ground lug. <br /> ohm. 5. Connect the shield of the RS-485 cable to the ground lug. <br /> •Connect the power supply wires in the power panel to a sepa- 6. RS-485 cable from master TLS RF. <br /> rate dedicated circuit. <br /> •Electrical rating power input-120 Vac or 240 Vac,50/60 Hz,2 �• See Figure 10 for connections. <br /> A max. <br /> •See Figure 2 for actual locations of power conduit knockouts <br /> into the unit.Power wiring must enter only in one of these <br /> knockouts. <br /> 2. AC power input wires(#14 AWG)to AC input terminals. <br /> in-is <br /> CARE Approved IOM 10-Veeder Root TLS RF Wireless Systems(W2)-Executive Order VR-202 <br />