Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ® Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: <br /> Sump/UDC ID 87 STP Sump Vent Sump <br /> Sump Manufacturer Bravo <br /> Sump Depth (inches) 60 32 <br /> Sump Bottom to Top of 18 12 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 9:16am 9:1 lam <br /> Initial Reading 4.39666 4.00706 <br /> Test End Time 9:31 am 9:26am <br /> Final Reading 4.39719 4.00763 <br /> Change in Reading 0.00053 0.00057 <br /> Pass Fail Criteria 0.002 0.002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />