Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8 . SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ® Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used : <br /> Sump/UDC ID 87 STP Sump Vent Sump <br /> Sump Manufacturer Bravo <br /> Sump Depth ( inches ) 60 32 <br /> Sump Bottom to Top of 18 12 <br /> Highest Pipe Penetration <br /> ( inches ) <br /> Test Start Time 9 : 16am 9 : 11 am <br /> Initial Reading 4 . 39666 4 . 00706 <br /> Test End Time 9 : 31am 9 : 26am <br /> Final Reading 4 . 39719 4 . 00763 <br /> Change in Reading 0 . 00053 0 . 00057 <br /> Pass/Fail Criteria 0 . 002 0 . 002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/ UDC ID <br /> Sump Manufacturer <br /> Sump Depth ( inches ) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> ( inches ) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail' and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section . <br /> Page 3 of 5 <br />