Laserfiche WebLink
UNDERGROUND STORAGE TANK <br /> SECONDARY CONTAINMENT TESTING REPORT FORM (Page 6 of 6) <br /> XXI. UNDER-DISPENSER CONTAINMENT TESTING INFORMATION <br /> Manufacturer(s): Identify UDC ID from section III for each Manufacturer <br /> 1 ® 2 ® 3 ® 4 ® 5 ❑ 6 ❑ <br /> 7 E 8 E 9 E 100 11 ❑ 12 El <br /> 1 E 2 E 3 E 4 ❑ 5 ❑ 6 ❑ <br /> 7 E 8 E 9 E 100 11 ❑ 12 El <br /> Test Method Used: <br /> ❑ Manufacturer Guidelines: (Specify) <br /> ® Industry Code or Engineering Standard: (Specify) Hydrostatic <br /> ❑ Engineered Method: (Specify) <br /> Attach the testing procedures and all documentation required to determine the results. #of Attached Pages5 <br /> UDC Testing Training and Certifications(List applicable certifications.) Expiration Date <br /> Caldwell Level Change Indicator 05/31/2022 <br /> XXII. COMMENTS <br /> Provide any additional comments here. <br /> All four UDCs failed the hydrostatic test due to either missing/removed or damaged Total Containment chase <br /> pipe plugs. Must further inestigate and or repair and retest with passing result. <br /> If the facility has more components than this form accommodates,additional copies of these pages may be attached. <br /> UDC=Under-dispenser containment,ID=Identification <br />