My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
SR0083332_SSNL
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
B
>
BOWMAN
>
76
>
2600 - Land Use Program
>
SR0083332_SSNL
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
3/3/2021 10:06:19 AM
Creation date
3/3/2021 9:45:35 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2600 - Land Use Program
FileName_PostFix
SSNL
RECORD_ID
SR0083332
PE
2602
FACILITY_NAME
76 W BOWMAN RD
STREET_NUMBER
76
Direction
W
STREET_NAME
BOWMAN
STREET_TYPE
RD
City
FRENCH CAMP
Zip
95231
APN
19326019
ENTERED_DATE
2/25/2021 12:00:00 AM
SITE_LOCATION
76 W BOWMAN RD
P_LOCATION
99
P_DISTRICT
003
QC Status
Approved
Scanner
SJGOV\tsok
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
73
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
percolation test must demonstrate a satisfactory percolation rate within the proposed <br /> septic system disposal field. <br /> Details and results of the percolation test are summarized in the following table. <br /> Table 2. Percolation Test Summary <br /> Test No., Percolation Test Percolation Rate Test Duration Comments <br /> Date Tested Depth (ft.) (minutes/inch) (see notes) <br /> P1, <br /> 2/16/2021 3.17 4.39 1 hr. Satisfactory perc. <br /> Shallow Test rate <br /> Note: A satisfactory percolation rate for a "shallow" test is greater than 1 but less than or equal to 60 minutes per <br /> inch. <br /> 1 Per San Joaquin County Environmental Health Department, a rate between 1.0 and 5.0 min/in requires a <br /> 20-foot separation between the bottom of dispersal system and ground water, or mitigation by system <br /> design or enhancement. <br /> Discussion of Percolation Test Results <br /> The soils within the proposed sewage disposal area of the Site have demonstrated a <br /> satisfactory percolation rate for the use of a septic system in accordance with the <br /> requirements of the San Joaquin County Environmental Health Department. This <br /> percolation test is considered representative of soils within a 100-foot radius of the test <br /> location. <br /> Because of the percolation rate between 1.0 and 5.0 min/in encountered in the test <br /> hole, the San Joaquin County Environmental Health Department will require a 20-foot <br /> separation from the bottom of the dispersal system to ground water, unless mitigated by <br /> system design or enhancement. <br /> Discussion of Septic System Sizing <br /> Septic system construction utilizing leach lines or a filter bed should follow the San <br /> Joaquin County On-Site Wastewater Treatment Systems Standards (2017) where <br /> applicable. <br /> LOGE 2109 Page 7 <br />
The URL can be used to link to this page
Your browser does not support the video tag.