Laserfiche WebLink
7. LINE LEAK DETECTOR TESTING <br />n Check this box if line leak detectors ARE NOT installed. (Do not complete this sect'to4 <br />Simulated release rate verified: (Check all that apply.) <br />X 3 GPH N 0.1 GPH N 0.2 GPH Yes No NA <br />Has the testing apparatus been properly calibrated?X T I <br />For emergency generator tank systems, does the LLD create an audrble and vrsual <br />alarm when a leak is detected?n n X <br />For mechanical LLDs, does the LLD restrict the flow through the prpe wl-ren a <br />release is detected?x tr tr <br />For electronic LLDs, does the turbine automatically shut off when a release is <br />detected?!tr X <br />hor electronlc LLlJs, does the turbine automatically shut off if any portion of the <br />monitoring system is disabled or disconnected?!r X <br />l-or electronic LLDs, does the turbine automatically shut off if any portion of the <br />monitoring system mqlfunctions or fails a tightness test?n tr x <br />For electronic LLDs, have all accessible wiring connections been visually inspected <br />for kinks and breaks?!n x <br />Were all items on the equipment manufacturer's maintenance checklist completed?X n n <br />were all LLDs confirmed operational within regulatory requirements?X tr D <br />LLD ID LLD Model Lines Monitored Pass Fail <br />T1 vMt 991D2000 87 PRODUCT x n <br />T2 vMt 99LD2000 91 PRODUCT X n <br />T3 vMt 99LD2000 DIESEL PRODUCT x n <br />T n <br />n n <br />n n <br />n n <br />n tr <br />!! <br />!T <br />n n <br />tr n <br />U nderg round Storage Tan k <br />Monitoring System Ceftification Form <br />Describe all answers marked "No" or "Fail" and proposed remedy in section g. <br />List all monitoring equipment either replaced or repaired in section g <br />Page 4 of 6