Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 6. TANK SECONDARY CONTAINMENT TEST <br /> Test Method Developed by 0 Manufacturer r Industry Standard 0 Professional Engineer <br /> Test Type Pressure 0 Vacuum ❑ Hydrostatic <br /> Test Equipment Used: <br /> Tank ID 87-91 Gasoline Diesel <br /> Tank Manufacturer Modern Modern <br /> Tank Capacity 6K-4K 12K <br /> Test Start Time 10:04 10:16 <br /> Initial Reading 7 Hg 7 Hg <br /> Test End Time 11:04 11:16 <br /> Final Reading 7 Hg 7 Hg <br /> Change in Reading 0 0 <br /> Pass/Fail Criteria +/- 0 +/- 0 <br /> Tightness Test Results 0 Pass ❑ Fail 0 Pass © Fail M Pass 0 Fail © Pass ❑ Fail <br /> 7. PIPE SECONDARY CONTAINMENT TEST <br /> Test Method Developed by 0 Manufacturer 0 Industry Standard 0 Professional Engineer <br /> Test Type Pressure © Vacuum 0 Hydrostatic <br /> Test Equipment Used: Pressure Decay Mechanical Gauge <br /> Pipe Run ID 87 Product 91 Product Diesel Product <br /> Pipe Manufacturer Ameron Ameron Ameron <br /> Test Start Time 09:31 09:40 09:46 <br /> Initial Reading x 5 psig 5 psig <br /> Test End Time x 10:40 10:46 <br /> Final Reading 0 psig 5 psig 5 psig <br /> Change in Reading x 0 0 <br /> Pass/Fail Criteria +/- 0 +/- 0 +/- 0 <br /> Tightness Test Results 0 Pass Fail Pass © Fail E Pass ❑ Fail 0 Pass ❑ Fail <br /> jj Pipe Run ID <br /> Pipe Manufacturer <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results 0 Pass ❑ Fail C Pass ❑ Fail 0 Pass © Fail I❑ Pass © Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 2 of 5 <br />