Laserfiche WebLink
1115000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2345989 Date: 4/14/2020 <br /> Site Name/ID: Love's County#538/538 <br /> Address: 15250 Thornton Rd <br /> City: Lodi State: CA Zip: 95242 <br /> Tank ID T1 T2 T3 <br /> Product UNLEADED PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 14 14 14 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLD Veeder Root PLLD <br /> Serial No. 365393 368217 375073 <br /> Pump Operating Pressure(psi) 33.00 36.00 40.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI <br /> *N/A for Electronic LD's <br /> Resiliency(ml) <br /> *N/A for Electronic LD's <br /> Metering PSI <br /> *N/A for Electronic LD's <br /> Opening Time(sec) <br /> *N/A for Electronic LD's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Clint Fuhrman Certification#: 96737 <br /> Technician Signature: Expire Date: 2/4/2022 <br /> Environmental Compliance for Petroleum Systems <br /> @2020 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />