Laserfiche WebLink
IkA CO <br /> South San Joaquin County Fire Authority <br /> Community Risk Reduction Division 835 Central Avenue <br /> FIRE Tracy , CA 95376 <br /> PH : ( 209) 83 1 - 6707 <br /> FAX : ( 209) 83 1 - 6703 <br /> fire . plancileck2( sicfire . org <br /> Date : 7 / 25 / 2022 <br /> Project # : PA - 2000045 <br /> Project Description : Site Approval : Neighborhood Referral <br /> Project Address : 5225 W. Eleventh St . , Tracy <br /> Jurisdiction : San Joaquin County <br /> At this time, project is conditionally approved subject to satisfying the following requirements . <br /> 1 . Prior to construction , applicant shall submit construction documents to the South San Joaquin <br /> County Fire Authority for review and approval . <br /> a . Construction documents shall be designed to the current edition of the California Code of <br /> Regulations , Title 24 , as amended by the City of Tracy Municipal Code . <br /> b . Deferred submittals for fire alarm , fire sprinkler, fire protection water supply, shall be listed <br /> on the coversheet of each page . Each deferred submittal shall be submitted , reviewed and <br /> approved by SSJCFA prior to installation . <br /> c . Fire protection water supply must be submitted separately from construction permit . All <br /> piping and installation shall be in accordance with CFC § 507 & NFPA standards . Approval of <br /> grading and / or on - site improvements does not grant installation of underground fire <br /> service . <br /> d . Fire sprinklers shall be designed by a licensed fire protection contractor or engineer . <br /> Hydraulic calculations , specifications and plans shall be submitted prior to issuance of <br /> building permit . <br /> e . Fire department connections shall be installed in accordance with CFC § 912 and NFPA <br /> standards . A hydrant shall be placed within 100' of the FDC, in accordance with NFPA 14 <br /> § 6 . 4 . 5 . 4 . FDC locations shall be approved by the fire code official prior to issuance of <br /> construction permit . <br /> f . Fire control room locations shall be approved the fire code official prior to the issuance of <br /> construction permit . <br /> g . Provide a truck turning template which clearly shows the truck turning radius of 29 ' - 9 " inside <br /> and 47 ' - 7 " outside . Truck turning template shall show all ingress and egress paths available . <br /> South San Joaquin County Fire Authority ■ ■ <br />