Laserfiche WebLink
Underground Storage Tank <br /> " sant Inspection Report Farm <br /> 6. OVERFILL PREVENTION EQUIPMENT DETAILS <br /> Tank ID (One OPE per column) 12K DSL <br /> Are both vent and tank riser piping ❑ Yes ❑ Yes ❑ Yes ❑ Yes <br /> secondarily contained? ® No ❑ No ❑ No ❑ No <br /> OPE Model OPW <br /> Tank Manufacturer Xerxes <br /> ® Shuts off ❑ Shuts off ❑ Shuts off ❑ Shuts off <br /> Flow Flow Flow Flow <br /> What is the OPE response when ❑ Restricts ❑ Restricts ❑ Restricts ❑ Restricts <br /> activated? Flow Flow Flow Flow <br /> (Check all that apply.) ❑ Audible ❑ Audible ❑ Audible ❑ Audible <br /> Alarm Alarm Alarm Alarm <br /> ❑Visual ❑Visual ❑Visual ❑Visual <br /> Alarm Alarm Alarm Alarm <br /> Are flow restrictors installed on vent ❑ Yes ❑ Yes ❑ Yes ❑ Yes <br /> piping that may interfere with the OPE <br /> operation? ® No E] No F] No E] No <br /> At what level in the tank is the OPE set to 7811 <br /> activate? (Inches from bottom of tank) <br /> What is the percent capacity of the tank in 93% <br /> which the OPE activates? <br /> Is the OPE in proper operating condition <br /> to respond when the stored substance ® Yes F-1 Yes El Yes ❑ Yes <br /> reaches the designated regulatory level? El No ❑ No El No El No <br /> 7. SUMMARY OF TESTING RESULTS <br /> OPE Inspection Results ® Pass ❑ Pass ❑ Pass ❑ Pass <br /> ❑ Fail ❑ Fail TE] Fail ❑ Fail <br /> 8. COMMENTS <br /> Removed old drop tube and built new drop tube to correct overfill specs. Tested and passed. <br /> Page 2 of 2 <br />