Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: INCON TS1000- 15 MIN. <br /> Sump/UDC ID DSL 1 DSL 2 1 2 <br /> Sump Manufacturer Unknown Unknown Unknown Unknown <br /> Sump depth (inches) N/A N/A N/A N/A <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration N/A N/A N/A N/A <br /> (inches) <br /> Test Start Time 10:27 11:23 1:00 1:29 <br /> Initial Reading 2.0560 3.2254 2.2867 3.2369 <br /> Test End Time 10:43 11:38 1:15 1:44 <br /> Final Reading 2.0546 2.2246 2.2866 3.2357 <br /> Change in Reading .0014 .0012 .0001 .0012 <br /> ass Fail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID 1 SAT <br /> Sump Manufacturer Unknown <br /> Sump depth (inches) N/A <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration N/A <br /> (inches) <br /> Test Start Time 12:02 <br /> Initial Reading 1.1456 <br /> Test End Time 12:17 <br /> Final Reading 1.1456 <br /> Change in Reading 0 <br /> Pass/Fail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> Page 4 of 6 <br />