Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ©✓ Manufacturer ❑r Industry Standard El Professional Engineer <br /> Test Type © Pressure El Vacuum E Hydrostatic <br /> Test Equipment Used: <br /> Sump/UDC ID 87 STP 91 STP Diesel STP <br /> Sump Manufacturer Unknown Unknown Unknown <br /> Sump Depth (inches) 49 49 45 <br /> Sump Bottom to Top of 9 9 9 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 09:07 09:24 10:58 <br /> Initial Reading 4.7192 4.5441 3.6936 <br /> Test End Time 09:22 09:40 11:14 <br /> Final Reading 4.7186 4.5440 3.6929 <br /> Change in Reading 0.0007 0.0001 0.0007 <br /> Pass/Fail Criteria +/-0.002 +/-0.002 +/-0.002 <br /> Tightness Test Results r Pass rl Fail F1 Pass El Fail © Pass 0 Fail Pass ❑� Fail <br /> Sump/UDC ID UDC 1-2 UDC 3-4 <br /> Sump Manufacturer Bravo Bravo <br /> Sump Depth (inches) 9 9 <br /> Sump Bottom to Top of Bottom Bottom <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 09:07 09:07 <br /> Initial Reading 0.9993 1.3768 <br /> Test End Time 09:22 09:22 <br /> Final Reading 0.9986 1.3772 <br /> Change in Reading 0.0007 0.0004 <br /> Pass/Fail Criteria +/-0.002 +/-0.002 <br /> Tightness Test Results © Pass Q Fail © Pass Q Fail 0 Pass © Fail C Pass C Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3of5 <br />