<br />Underground Storage Tank <br />Secondary Containment Testing Report Form <br />All tests marked “Fail” and any repairs made before or during the tightness test must be described in <br />the COMMENTS section. <br />Page 3 of 5 <br />Test Method Developed by ☐ Manufacturer ☐ Industry Standard ☒ Professional Engineer <br />Test Type ☐ Pressure ☐ Vacuum ☒ Hydrostatic <br />Test Equipment Used: Caldwell Level Change Indicator <br /> <br />Sump/UDC ID 1-87-PS 2-91-PS 3-Diesel-PS <br />Sump Manufacturer Unknown FGC Unknown FGC Unknown FGC <br />Sump Depth (inches) 39" 39" 37 1/2" <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />11" 18" 12" <br />Test Start Time 10:07 9:25 9:30 <br />Initial Reading .001 .001 .001 <br />Test End Time 10:37 9:55 10:00 <br />Final Reading .001 .001 .001 <br />Change in Reading 0 0 0 <br />Pass/Fail Criteria > .002 > .002 > .002 <br />Tightness Test Results ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☐ Pass ☐ Fail <br /> <br />Sump/UDC ID UDC 1&2 UCD 3&4 UDC 5&6 UDC 7&8 <br />Sump Manufacturer Environ Environ Environ Environ <br />Sump Depth (inches) 29" 29" 29" 29" <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />13" 13" 14" 14" <br />Test Start Time 9:48 9:44 9:57 9:52 <br />Initial Reading .001 .001 .001 .001 <br />Test End Time 10:18 10:14 10:27 10:22 <br />Final Reading .001 .001 .001 .001 <br />Change in Reading 0 0 0 0 <br />Pass/Fail Criteria > .002 > .002 > .002 > .002 <br />Tightness Test Results ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail <br /> <br />Additional copies of this page may be attached. <br /> <br />8. SUMP/UDC TEST