Laserfiche WebLink
A NJ O A Q U l N Environmental Health Department <br /> COUNTY— <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> GSG GAS&MART 701 E DR MARTIN LUTHER KING JR BLVD, June 16, 2021 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 116 CCR 2637.1(d), 2637.1(e)Failure to submit the"Spill Container Testing Report Form"within 30 days. <br /> OBSERVATION:Annual spill container testing was performed on 6/29/2020 and a test report was submitted on <br /> 8/17/2020, 1 month late. <br /> REGULATION GUIDANCE:A copy of the test report must be submitted within 30 days of the tests. <br /> CORRECTIVE ACTION: Take all necessary precautions to ensure testing and submittal of test reports are <br /> performed in a timely manner. <br /> This is a minor violation. <br /> 118 CCR 2637.2(d&e), 2665(a&b) Failure to submit the"Overfill Prevention Equipment Inspection Report Form"within <br /> 30 days. <br /> OBSERVATION: Overfill testing was performed on 5/20/2020 during a service request inspection (SR0081338).A <br /> test report has not been submitted to the EHD or the California Environmental Reporting System (CERS). <br /> REGULATION GUIDANCE:A copy of the test report must be submitted within 30 days of the test. <br /> CORRECTIVE ACTION: Immediately provide this report to the EHD. <br /> This is a minor violation. <br /> 203 CCR 2712(b)(1-2)Failure to maintain monitoring records for 36 months and maintenance records for 60 months. <br /> OBSERVATION: Maintenance and monitoring records for the last three years were not found on site. <br /> -2020 Monitoring System Certification test results <br /> -Overfill Prevention Equipment test results <br /> REGULATION GUIDANCE: These records shall be maintained on site for at least three years. Monitoring records <br /> include: (1)date and time of all monitoring or sampling; (2)monitoring equipment calibration and maintenance <br /> records; (3)results of any visual observations; (4)results of sample analysis performed a lab or in the field; (5)logs <br /> of all readings of gauges or other monitoring equipment, ground water elevations, or other test results; (6)results of <br /> inventory readings and reconciliations. <br /> CORRECTIVE ACTION: Immediately locate and maintain all missing maintenance and monitoring records for the <br /> last three years on site and submit copies to the EHD. <br /> This is a minor violation. <br /> FA0002512 PR0231059 SCO01 06/16/2021 <br /> EHD 23-01 Rev.9/16/2020 Page 5 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />