Laserfiche WebLink
(E� <br /> JONES COVEY GROUP, INC. <br /> V 9VE LO P 9 RS/CONSTRUCTORS <br /> MECHANICAL / ELECTRONIC LEAK DETECTOR CERTIFICATION <br /> SITE: Pilot Flying J 618 Ripon DATE: 05 18 2 0 2 1 <br /> State Facility# CONTACT: Manager <br /> 1501 N. Jack Tone Road Ripon CA 95366 PHONE: 209-599-4141 <br /> JOB#: 2136468-1-1 <br /> Tank # T-5 T-6 <br /> Product 91 Auto Diesel <br /> LD Manufacturer Red-Jacket Red-Jacket <br /> LD Model FX1 V FX1 DV <br /> Sump Condition Good Good <br /> Operation Pressure <br /> (PSI) 26 PSI 28 PSI <br /> Opening Time(Sec) 7 Sec 5 Sec <br /> Metering Pressure <br /> (PSI) 12 PSI 11 PSI <br /> Functional Element 18 PSI 17 PSI <br /> Holding Pressure <br /> Leak Rate LD Detected 3 GPH 3 GPH <br /> (GPH) <br /> Does LD Detect 3 GPH Yes Yes <br /> Leak Rate? <br /> LD Serial Unreadable Unreadable <br /> Comments: <br /> Technician Robert Bramhall License Number 3978 <br /> Signature <br /> 9595 Lucas Ranch Rd.# 100 Rancho Cucamonga, CA 91730 <br /> Office (909)972-7581 Fax (909) 484-0300 Fax California State License#804431 A,B,HAZ <br />