Laserfiche WebLink
Underground Storage Tank <br /> Overfill Prevention Equipment Inspection Report <br /> 6. OVERFILL PREVENTION EQUIPMENT DETAILS <br /> Tank ID (one OPE per column) T1 :Bio T2:Unleaded T3:Premium <br /> Are both vent and tank riser piping 521 Yes ❑ Yes ❑ Yes ❑ Yes <br /> secondarily contained? ❑ No 52 No 5? No ❑ No <br /> OPE Model OPW 71 SO-4" 708590 Defender Series 708590 Defender Series <br /> What is the OPE response when activated? [0 Shut off 52 Shut off 5? Shut off ❑ Shut off <br /> (Check all that apply.) Flow Flow Flow Flow <br /> ❑Restricts ❑Restricts ❑Restricts ❑Restricts <br /> Flow Flow Flow Flow <br /> ❑ Audible ❑ Audible ❑ Audible ❑ Audible <br /> Alarm Alarm Alarm Alarm <br /> ❑ Visual ❑ Visual ❑ Visual ❑ Visual <br /> Alarm Alarm Alarm Alarm <br /> Are flow restrictors installed on vent piping ❑ Yes* ❑ Yes* ❑ Yes* ❑ Yes* <br /> that may interfere with the OPE operation? 521 No 52 No 52 No ❑ No <br /> At what level in the tank is the OPE set to <br /> activate? Inches from bottom of tank 105 3/4" 102 1/2" 102 1/8" <br /> What is the percent capacity of the tank at <br /> 94.6% 93.4% 93.2% <br /> which the OPE activates? <br /> Is the OPE in proper operating condition to [0 Yes 52 Yes 52 Yes ❑ Yes <br /> respond when the stored substance ❑ No ❑ No ❑ No ❑ No <br /> reaches the designated regulatory level? <br /> 7. SUMMARY OF TESTING RESULTS <br /> OPE Inspection Results 52 Pass 52 Pass 52 Pass ❑ Pass <br /> ❑ Fail ❑ Fail ❑ Fail ❑ Fail <br /> 8. COMMENTS <br /> Describe all results marked "Fail"and each proposed remedy. <br /> * Mark here if: <br /> ❑ Flow restrictors interfere with overfill prevention and equipment repairs required. <br /> Additional copies of this page may be attached. <br /> Attach tank chart(s), measurements, calculations, and In-Tank Setup report(s) <br /> Page 2 of 2 <br />