Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> CCUNT <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> MORADA CHEVRON FAST N EASY#60* 10878 N HWY 99 , STOCKTON May 26, 2021 <br /> Single-Walled Non-Pressurized Piping <br /> 404 CCR 2643(e),2661(f) Failure to conduct 0.1 gph test on single-walled gravity piping biennially or post repair(pre-1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted General violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 104 CCR 2632(d)(1), 2634(d)Failure to have an approved UST Monitoring Plan. <br /> OBSERVATION: The monitoring plan is not current and/or not approved by the EHD. The monitoring plan lists <br /> Vaporless Red Jacket 99LD2000/FX-IV leak detectors for all USTs. VMI 99LD2000 leak detectors were observed <br /> on site for all LISTS. <br /> REGULATION GUIDANCE: The monitoring plan must be uploaded to the California Environmental Reporting <br /> System (CERS). <br /> CORRECTIVE ACTION: Immediately log into CERS, make the necessary changes, and submit for review by the <br /> EHD. <br /> This is a repeat violation, Class Il. <br /> 106 CCR 2632(d), 2641(h) Failure to submit and maintain a current facility plot plan/site map. <br /> OBSERVATION:An accurate UST Monitoring Site Plan was not submitted. The monitoring site plan does not <br /> clearly identify the monitoring devices for the system. The Site Plan has Red Jacket leak detectors listed. Red <br /> Jacket leak detectors were not observed on site. <br /> REGULATION GUIDANCE:A site plan must be submitted identifying the locations where monitoring will be <br /> performed. The site plan must show the general layout of tanks and piping and clearly identify locations of the <br /> following equipment, if installed: 1)monitoring system control panels; 2)in-tank liquid level probes (if used for leak <br /> detection); 3)devices monitoring tank annular spaces or vault;4)devices monitoring product piping; 5)devices <br /> monitoring fill piping; 6)devices monitoring vent piping; 7)devices monitoring vapor recovery piping; 8)devices <br /> monitoring vent/transition sumps; 9)devices monitoring under-dispenser containment; 10)line leak detectors; and <br /> 11)devices monitoring any other secondary containment areas. <br /> CORRECTIVE ACTION: Immediately log into the California Environmental Reporting System (CERS)at <br /> http://cers.calepa.ca.gov/and upload a copy of the UST Monitoring Site Plan. <br /> This is a repeat violation, Class Il. <br /> FA0001146 PR0231598 SCO01 05/26/2021 <br /> EHD 23-01 Rev.9/16/2020 Page 4 of 9 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />