CONCLUSIONS AND RECOMMENDATIONS <br /> In summary, the soil conditions examined near the proposed septic system drain field <br /> were found to be suitable for a standard septic system utilizing leach lines with seepage <br /> pits. A satisfactory soil percolation rate of 27.8 min/in was observed in the deep soil <br /> zone at the test location. The soils in the test location were found to be a mixture of <br /> clay, silt, and sand. <br /> The depth of ground water based on recent aquifer levels is approximately 114 to 120 <br /> feet below ground surface. The ground-water flow is to the south at a rate of <br /> approximately 7 to 8 feet per mile in the vicinity of the Site. <br /> A water sample was collected from the domestic well on the Site as part of this <br /> investigation. Nitrate was detected in the sample at a concentration of 2.1 mg/L-N, well <br /> below the MCL of 10 mg/L-N. DBCP was not detected in the sample. Based on maps <br /> reviewed, neither nitrate nor DBCP appears to be a problem in nearby wells. <br /> Based on the methods and assumptions described, the nitrate loading calculation <br /> indicates that the use of on-site septic tanks and drain field systems on the Site has the <br /> potential to cause a buildup of nitrate in the aquifer up to 7.1 mg/L, below the maximum <br /> drinking water standard of 10 mg/L-N. Because of the favorable result of the nitrate <br /> loading calculation, no nitrate mitigation is recommended at this time. <br /> LOGE 2125 Page 13 <br />