GENERAL PLUMBING NOTES: PLUMBING FIXTURE AND EQUIPMENT SCHEDULE PLUMBING FIXTURE AND EQUIPMENT SCHEDULE
<br /> 1. THE INTENT OF THE DRAWINGS AND SPECIFICATIONS IS TO CONSTRUCT THE BUILDING IN ACCORDANCE WITH THE 2016 EDITION OF TITLE CONNECTION SIZES CONNECTION SIZES
<br /> 24, CALIFORNIA CODE OF REGULATIONS. SHOULD ANY CONDITIONS DEVELOP NOT COVERED BY THE CONTRACT DOCUMENTS WHEREIN MARK FIXTURE DESCRIPTION MARK FIXTURE DESCRIPTION w
<br /> S or W V CW HW S or W V CW HW
<br /> THE FINISHED WORK WOULD NOT COMPLY WITH SAID TITLE 24, CALIFORNIA CODE OF REGULATIONS, A CHANGE ORDER DETAILING AND
<br /> WATER KOHLER WALL MOUNT "BARDON"#K-4991-ET, 0.125 GPF, WITH Q co
<br /> SPECIFYING THE REQUESTED WORK SHALL BE SUBMITTED TO AND APPROVED BY DSA BEFORE PROCEEDING WITH THE WORK. WHA-1 MODEL 652-A SIOUX CHEIF, CONFORM TO PDI WH-201, ASSE 1010; =w
<br /> HAMMER - - - - STAINLESS STEEL SECURED STRAINER, "ZURN"#ZER6003A V-ULF-CPM 0Z
<br /> (A) TEMP TO 250°F, MAX 350 PSIG WORKING PRESSURE z
<br /> ARRESTOR BATTERY SENSOR FLUSH VALVE, (0.125 GPF), PROVIDE A STEEL v Q 2
<br /> 2. THE APPLICABLE CODES AND REGULATIONS FOR THIS PROJECT INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING: U-1 URINAL 2" 1-1/2" 3/4" - SUPPORT PLATE FOR MOUNTING FIXTURE PER DETAIL D/P2.0. CBC w Jv
<br /> CALIFORNIA CODE OF REGULATIONS TEMATURE ACCESS COMPLIANT MOUNTING HEIGHT SHALL BE 17" TO LIP, 2" vQ
<br /> MODEL LFUSG-8-M1 WATTS, MAX TEMP OUTLET 120°F, WITH BUILT-IN ® z LLp�
<br /> TMV-1 MIXING - - - - W.C.O. Q =per
<br /> TITLE 8, INDUSTRIAL RELATIONS VALVE CHECK VALVES, BRASS BODY, AND COP THERMOSTAT. O
<br /> �,cl� U)
<br /> TITLE 19, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS
<br /> TITLE 24 PART 1 ADMINISTRATIVE REGULATIONS TEMATURE MODEL LFUSG-B-M1 WATTS, MAX TEMP OUTLET 105°F, WITH BUILT-IN NOTES: a
<br /> 2016 CALIFORNIA BUILDING CODE, PART 2, TITLE 24 CCR TMV-2 MIXING - - - - A. SIZE MANUFACTURER'S RECOMMENDATION. o o w
<br /> CHECK VALVES, BRASS BODY, AND COP THERMOSTAT. B. CLEANOUT SHALL BE SAME SIZE AS PIPE BEING SERVED. `V r> <
<br /> 2016 CALIFORNIA ELECTRICAL CODE, PART 3, TITLE 24 CCR VALVE N o
<br /> 2016 CALIFORNIA MECHANICAL CODE, PART 4, TITLE 24 CCR C. THIS SCHEDULE IS COMPREHENSIVE. ALL MARKS MAYOR MAY NOT BE USED ON PLANS. N o ch cs 11
<br /> 2016 CALIFORNIA PLUMBING CODE, PART 5, TITLE 24 CCR TRAP MODEL 695 SIOUX CHEIF BRONZE PRIMER VALVE WITH REMOVABLE
<br /> TP-1 - - 1/2" - OA TING PARTS INTEGRAL VACUUM BREAKER, AND GASKETED Q
<br /> 2016 CALIFORNIA FIRE CODE, PART 9, TITLE 24 CCR PRIMER
<br /> ACCESS COVER. REFERENCE PLUMBING FIXTURE
<br /> NFPA 1012015 EDITION SCHEDULE FOR CONCEALED ARM ❑ ❑ ❑
<br /> OSHA - OCCUPATIONAL SAFETY AND HEALTH ACT REDUCED MODEL 975XL WILKINS OR MODEL RP200 CASH ACME, BRONZE BODY, CARRIER TO BE INSTALLED FOR
<br /> PRESSURE WITH SHUT-OFF VALVES, Y STRAINER, AND TEST COCKS. PROVIDE WALL MOUNTING LAVATORY, REFER This document, the ideas and
<br /> RP-1 BACKFLOW AIR GAP DRAIN AND ROUTE FULL SIZE DRAIN TO DISCHARGE INTO TO ARCHITECTURAL DETAILS. designs incorporated herein, are
<br /> 3. LAYOUT OF MATERIALS, EQUIPMENTAND SYSTEMS IS GENERALLY DIAGRAMMATIC UNLESS SPECIFICALLY DIMENSIONED. SOME WORK MAY PREVENTER MOP SINKsolely the property of VAI and is
<br /> .
<br /> BE SHOWN OFFSET FOR CLARITY. THE PLUMBING BUILDING PLANS HAVE BEEN PREPARED TO MATCH THE ARCHITECTURAL PLANS. IF not to be used, in whole or in
<br /> DIFFERENCES OCCUR, THE ARCHITECTURAL PLANS ARE TO TAKE PRECEDENCE. THE ACTUAL LOCATIONS OF ALL MATERIALS, PIPING, part for any project or
<br /> MODEL 861 SIOUX CHEIF WHITE PVC 12"X 12"FLOOR SINK WITH T duplication, without written
<br /> DUCTWORK, FIXTURES, EQUIPMENT, SUPPORTS, ETC. SHALL BE CAREFULLY PLANNED, PRIOR TO INSTALLATION OF ANY WORK, TO AVOID
<br /> FS-1 FLOOR SINK 3" 1-1/2" HEAVY DUTY PVC HALF GRATE, SEDIMENT BUCKET. PROVIDED WITH authorization.
<br /> ALL INTERFERENCE WITH EACH OTHER, OR WITH STRUCTURAL, ELECTRICAL, ARCHITECTURAL, OR OTHER ELEMENTS. ALL PIPE OFFSET 3"DRAIN AND 1 1/2" VENT. © COPYRIGHT 2019
<br /> ELBOWS FOR COORDINATION BETWEEN TRADES ARE NOT SHOWN. CONTRACTOR SHALL INCLUDE SUFFICIENT FUNDS FOR THE
<br /> " El El El El
<br /> OFFSETS IN THE BID. VERIFY THE PROPER VOLTAGE AND PHASE OF ALL EQUIPMENT WITH THE ELECTRICAL PLANS. ALL FLOOR MODEL 832-36PNQ SIOUX CHEIF 3"LIGHT DUTY DRAIN WITH 7"
<br /> CONFLICTS SHALL BE CALLED TO THE ATTENTION OF THE ARCHITECT AND THE ENGINEER PRIOR TO INSTALLATION OF ANY WORK OR THE FD-1 DRAIN 3 1-1/2" - - SQUARE TOP, PVC BODY WITH NICKEL BRONZE RING AND STRAINER. U � O � Ln
<br /> ORDERING OF ANY EQUIPMENT. PROVIDED WITH 3"DRAIN AND 1 1/2" VENT. �o N
<br /> 71- It-
<br /> 4. WHEN INSTALLING DRILLED-IN ANCHORS AND/OR POWDER-DRIVEN PINS IN EXISTING NON-PRESTRESSED CONCRETE, USE CARE AND MODEL 851 SIOUX CHEIF PVC BODY, ROUND HEAVY-DUTY CAST IRON ., �' C N N
<br /> FCO-1 FLOOR
<br /> CAUTION TO AVOID CUTTING OR DAMAGING THE EXISTING REINFORCING BARS. WHEN INSTALLING THEM INTO EXISTING PRE-STRESSED - - - - TOP, POLYPROPYLENE OR ABS PLUG, ADJUSTABLE TO FINISH �+ 1 ':t �� ccr)
<br /> (B) CLEANOUT �' '� � c/� •-4
<br /> CONCRETE (PRE- OR POST-TENSIONED), LOCATE THE PRESTRESSED TENDONS BY USING A NON-DESTRUCTIVE METHOD PRIOR TO SURFACE U ct
<br /> INSTALLATION. MAINTAIN A MINIMUM CLEARANCE OF ONE INCH BETWEEN THE REINFORCEMENT AND THE DRILLED-IN ANCHOR AND/OR PIN. `O ,r
<br /> YC-1 YARD MODEL 834 SIOUX CHIEF DURA-COATED CAST IRON,
<br /> (B) CLEANOUT - - - DOUBLE-FLANGED HOUSING, AND HEAVY-DUTY SCORIA TED U U U
<br /> 5. MEP COMPONENT ANCHORAGE NOTE: DUCTILE IRON COVER o w
<br /> ALL MECHANICAL, PLUMBING, AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND INSTALLED PER THE DETAILS ON THE DSA WCO-1 WALL MODEL 873 SIOUX CHIEF THREADED, COUNTERSUNK BRONZE � Z CJ0
<br /> - - - - CLEANOUT PLUG. PROVIDE DRILLED TAP FOR CENTER SCREW AND
<br /> APPROVED CONSTRUCTION DOCUMENTS. WHERE THERE IS NO DETAIL IS INDICATED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED CLEANOUT O !:., N
<br /> OR BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE 2016 CBC, SECTIONS 1616A.1.18 THROUGH STAINLESS STEEL COVER. U L w
<br /> 1616A.1.26 AND ASCE 7-10 CHAPTERS 13, 26 AND 30. AMERICAN STANDARD MODEL CADET 3483.001 (BOWL) 4142.100
<br /> (TANK)(L) 4142.801 (TANK)(R) FIXTURE AND HARDWARE PROVIDED
<br /> 1. ALL PERMANENT EQUIPMENT AND COMPONENTS. AND INSTALLED BY PLUMBING CONTRACTOR.12"ROUGH-IN, COLOR:
<br /> WATER _ WHITE AMERICAN STANDARD CADET OPEN FRONT SEAT, NO COVER.
<br /> 2. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLYATTACHED (E.G. HARD WIRED) TO THE BUILDING UTILITY SERVICES WC-1 CLOSET 4 2 1/2 17"RIM HEIGHT, FOR HANDICAPPED. PRESSURE ASSISTED 1.1 GPF.
<br /> SUCH AS ELECTRICITY, GAS OR WATER. MOUNT CONTROLS ON ACCESSIBLE SIDE OF TOILET. CONTRACTOR
<br /> TO COORDINATE WITH FIXTURE SUPPLIER FOR LEFT/RIGHT HAND
<br /> 3. MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS AND HEAVIER THAN 400 POUNDS OR HAS A FLUSH LEVER TO COMPLY WITH ADA REQUIREMENTS.
<br /> CENTER MASS LOCATED 4 FEET OR MORE ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT
<br /> ARE REQUIRED TO BE ANCHORED WITH TEMPORARY ATTACHMENTS. KHOLER BRENHAM K-1997-4 FIXTURE AND HARDWARE PROVIDED
<br /> AND INSTALLED BY PLUMBING CONTRACTOR. WALL-MOUNT WITH
<br /> THE ATTACHMENT OF THE FOLLOWING MECHANICAL, PLUMBING, AND ELECTRICAL COMPONENTS SHALL BE POSITIVELY ATTACHED TO ZURN Z1231 CONCEALED ARM CARRIER, 4"CENTERS WITH CHROME
<br /> THE STRUCTURE, BUT NEED NOT BE DETAILED ON THE PLANS. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED T&S MODEL EC-3103 MOTION ACTIVATED FAUCET(EF-1 ITEM#478),
<br /> BETWEEN THE COMPONENTAND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT. LAV-1 LAVATORY 1 1/4" 1 1/4" 1/2" 1/2" B-0199-03-N05AERATOR (0.5 GPM). FAUCET INCLUDES AC/DC
<br /> CONTROL MODULE W/INTEGRAL FLOW CONTROL SETTING,
<br /> A. COMPONENTS WEIGHING LESS THAN 400 POUNDS AND HAVE A CENTER MASS LOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR TEMATURE CONTROL MIXING VALVE SET TO 105°F W/INTEGRAL ❑ ❑ ❑ ❑
<br /> OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT. CHECK VALVES, 18"STAINLESS STEEL FLEXIBLE HOSES. INSTALL
<br /> KOHLER BRENHAM SHROUD K-1998. REF ARCHITECTURAL DRAWINGS
<br /> FOR ROUGH-IN ELEVATIONS.
<br /> B. COMPONENTS WEIGHING LESS THAN 20 POUNDS, OR IN THE CASE OF DISTRIBUTED SYSTEMS, LESS THAN 5 POUNDS PER FOOT, WHICH . Yr), p
<br /> ARE SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A WALL. '` - > w
<br /> MODEL FIAT MSB-2424 FIXTURE AND HARDWARE PROVIDED AND ,� > 00 z z
<br /> INSTALLED BY PLUMBING CONTRACTOR. NO. 830AA FAUCET WITH
<br /> MS-1 MOP SINK 3" 1 1/2 1/2" 1/2" � �
<br /> " I w J
<br /> FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPROVED DRAWINGS, THE INSTALLATION SHALL BE SUBJECT TO THE INTEGRAL VACUUM BREAKER,NO.832-A HOSE AND BRACKET, r,, Zi
<br /> APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD AND THE DSA DISTRICT STRUCTURAL ENGINEER. THE PROJECT INSPECTOR WILL NO.1453BB FLOOR STRAINER AND NO. 899-CC MOP HANGER.
<br /> VERIFY THAT ALL COMPONENTS AND EQUIPMENT HAVE BEEN ANCHORED IN ACCORDANCE WITH ABOVE REQUIREMENTS. \� \�, `��._�EI.> `�� 3
<br /> FIXTURE AND HARDWARE OWNER FURNISHED, INSTALLED BY
<br /> 6. PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE: PLUMBING CONTRACTOR. ADA COMPLIANT, STAINLESS STEEL
<br /> S-1 SINK 1 1/2" 1 1/2" 1/2" 1/2" FIXTURE, BRASS FAUCET& P-TRAP. PROVIDED WITH STOP VALVES,
<br /> PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH THE FORCES AND DISPLACEMENTS - FLEXIBLE SUPPLY RISERS, TRUBRO LAV GUARD 2 PROTECTIVE PIPE ❑ ❑ ❑ ❑
<br /> PRESCRIBED IN ASCE 7-10 SECTION 13.3 AS DEFINED IN ASCE 7-10 SECTION 13.6.5.6, 13.6.7, 13.6.8, AND 2016 CBC, SECTIONS 1616A.1.24, COVERS ON EXPOSED HOT WATER AND DRAIN LINES AND
<br /> 1616A.1.25, 1616A.1.26. TEMA TURE-ACTUA TING MIXING VALVE& SET TO 105' F,
<br /> THE METHOD OF SHOWING BRACING AND ATTACHMENTS TO THE STRUCTURE FOR THE IDENTIFIED DISTRIBUTION SYSTEM ARE AS NOTED MODEL PL-SHS-1 SELECT STAINLESS FIXTURE AND HARDWARE
<br /> BELOW. WHEN BRACING AND ATTACHMENTS ARE BASED ON A PREAPPROVED INSTALLATION GUIDE (E.G., SMACNA OR OSHPD OPM), OWNER FURNISHED, INSTALLED BY PLUMBING CONTRACTOR.COMPLIANT, CUSTOM WALL MOUNT 10 FRONT TO BACK X 14W X 6 ADA
<br /> „D
<br /> COPIES OF THE BRACING SYSTEM INSTALLATION GUIDE OR MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF AND HAND SINK,PRODUCTION LINE. PROVIDED WITH BRASS FAUCET
<br /> DURING THE HANGING AND BRACING OF THE DISTRIBUTION SYSTEMS. THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE S-2 SINK 1 1/2" 1 1/2" 1/2" 1/2" SUPPLIER PART#B-1146 & P-TRAP, INSTALL TRUEBRO LAV GUARD 2 d
<br /> ADEQUACY OF THE STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS. PROTECTIVE PIPE COVERS ON EXPOSED HOT WATER AND DRAIN
<br /> LINES, STOP VALVES AND TEMA TURE-ACTUA TING MIXING VALVE&
<br /> SET TO 105' F.
<br /> MP MD PP A. OPTION 1: DETAILED ON THE APPROVED DRAWINGS WITH PROJECT SPECIFIC NOTES AND DETAILS.
<br /> MODEL TSA-3-D1-711 TURBO AIR BOWL SIZE 12'x19'x12", FIXTURE AND ❑ ❑ ❑ ❑
<br /> MP El MD❑ PP® B. OPTION 2: PLUMBING PIPING (PP) - SHALL COMPLY WITH OPM-0043-13 OSHPD PRE-APPROVAL (MASON WEST, HARDWARE OWNER FURNISHED, INSTALLED BY PLUMBING CD
<br /> SEISMIC RESTRAINT GUIDELINES FOR SUSPENDED DISTRIBUTION SYSTEMS). SS=3 SINK 3" 2" 1/2" 1/2" CONTRACTOR. PROVIDED WITH T&S MODEL MPY8WLN-08CR 8" r I�
<br /> FAUCET(EF-1 ITEM#600), P-TRAP AND STOP VALVES. v rn
<br /> MP MD PP C. SHALL COMPLY WITH THE SMACNA SEISMIC RESTRAINT MANUAL, OSHPD EDITION (2009), INCLUDING ANY z ' Q
<br /> ADDENDA. FASTENERS AND OTHER ATTACHMENTS NOT SPECIFICALLY IDENTIFIED IN THE SMACNA SEISMIC MODEL 71000 JOSAM FIXTURE AND HARDWARE PROVIDED AND z
<br /> RESTRAINT MANUAL, OSHPD EDITION, ARE DETAILED ON THE APPROVED DRAWINGS WITH PROJECT SPECIFIC FREEZE-PROOF INSTALLED BY PLUMBING CONTRACTOR. BOX TYPE, CAST BRONZE,INTEGRAL VACUUM BREAKER-BACK FLOW PREVENTER, "T"HANDLE, Q O
<br /> NOTES AND DETAILS. THE DETAILS SHALL ACCOUNT FOR THE APPLICABLE SEISMIC HAZARD LEVEL A AND FPWH-1 WALL - - 3/4" - Z (n
<br /> CONNECTION LEVEL 8 FOR THE PROJECT AND CONDITIONS. HYDRANT POLISHED FACE, HINGED LOCKING COVER, BRONZE WALL CASTING, J J U
<br /> RENEWABLE SEAT, BRONZE OATING PARTS, I"N.P.T. INLET, AND 3/4" Q LU
<br /> BRACE ALL PIPING 3"DIAMETER AND GREATER; USE Ip=1.0 FOR SEISMIC DESIGN CALCULATIONS. EXCEPTION: NATURAL GAS PIPING H.P.T. OUTLET. D z U co
<br /> 1" DIAMETER AND GREATER TO COMPLY WITH DSA BULLETIN BU 11-03; USE Ip=1.5 FOR SEISMIC DESIGN CALCULATIONS. ••
<br /> MODEL SC8 WATTS FIXTURE AND HARDWARE PROVIDED AND M � 0
<br /> INSTALLED BY PLUMBING CONTRACTOR. CAST BRASS THREADEDW Y Z
<br /> 7. PENETRATIONS THROUGH FIRE RATED WALLS, FLOOR/CEILING, AND ROOF/CEILING ASSEMBLIES SHALL BE SEALED USING AN APPROVED SILLCOCK WITH FLANGECAST IRON HANDWHEELAND Z U Q
<br /> , ,
<br /> SYSTEM CAPABLE OF PREVENTING THE PASSAGE OF FLAMES AND HOT GASES WHEN SUBJECTED TO THE REQUIREMENTS OF THE TEST HB-1 HOSE BI88 - - 3/4" - TAMPER-PROOF VACUUM BREAKER. 3/4"N.P.T. INLET, AND 3/4"H.P.T. Q
<br /> STANDARD SPECIFIC TO FIRE STOPS PER 2016 CBC SECTION 714. THIS INCLUDES EXISTING PIPE AND CONDUIT THROUGH NEW OUTLET. PROVIDED WITH 25 FOOT HOSE AND SPRAY GUN. MOUNT 24" LU 0 W
<br /> ASSEMBLIES. CUSTOM DESIGNED SYSTEMS WHICH COMBINE COMPONENTS FROM DIFFERENT APPROVED SYSTEMS BUT HAVE NOT BEEN AFF. wJ
<br /> TESTED AS A COMPLETE ASSEMBLY WILL NOT BE ACCEPTABLE. FOR FIRE STOPS FOR PIPE PENETRATIONS SEE SPECIFICATIONS AND /� Q Q
<br /> V) DETAILS A,E/P-6. MODEL GB1 SCHIER PRODUCTS SEAMLESS MOLDED POLYETHYLENE W
<br /> GREASE TANK, 3"FPT INLET/OUTLET WITH 3"X2"FPT FITTINGS, 25 GPM, 10 =
<br /> 8. FIELD VERIFY THE EXACT LOCATION, DEPTH AND SIZE OF ALL NEW POINTS OF CONNECTION TO EXISTING UTILITIES PRIOR TO GI-1 - - 3" - GALLON LIQUID INTERCEPTOR CAPACITY, 64.9 LBS GREASE CAPACITY, FACTORY O UJ W0(n
<br /> �
<br /> COMMENCING NEW UTILITY WORK. BUILT-IN FLOW CONTROL, INTEGRAL AIR RELIEF/ANTI-SIPHON, ASME 0. JW
<br /> A112.14.3 AND CSA B481.1 CERTIFIED. O U 2 Z
<br /> 9. INSTALLATION OF NEW UTILITIES FROM EXISTING MAINS IN THE STREET SHALL BE DONE IN STRICT ACCORDANCE WITH GOVERNING QROFESS/ UJ -
<br /> AUTHORITY REQUIREMENTS. RHEEM MODEL ELDS52, 47 GALLON, 9 kW, 280 VOLT 3-PHASE WITH 120 t�0 n l�, m
<br /> DEG. F OUTLET TEMPERATURE. PROVIDE WITH AMTROL (OR EQUAL) 'WA TER \�� § 2
<br /> 10. INSTALLATION, TYPE AND MANUFACTURERS MODELS OF DOMESTIC WATER METERS, BACKFLOW PREVENTERS, FIRE HYDRANTS, WH 1 HEATER - - - - EXPANSION TANK AND DRAIN PAN SIZED PER MANUFACTURERS 3 �^ co J
<br /> DETECTOR CHECK VALVES, MANHOLES, DRAIN INLETS/OUTLETS AND OTHER APPURTENANCE OF SITE UTILITY SYSTEMS SHALL BE DONE IN RECOMMENDATION. TO BE WIRED FOR SIMULTANEOUS OPERATION. ! I` O_
<br /> MOUNT WATER HEATER ON SUPPORT PLATFORM, REF. B/P2.1
<br /> STRICT ACCORDANCE WITH GOVERNING AUTHORITY REQUIREMENTS. rte. 9- -2021 ❑ ❑ ❑ ❑
<br /> 11. CONTRACTOR SHALL EXCAVATE AND BACKFILL THE GAS SERVICE TRENCH FOR THE LOCAL GAS UTILITY. THE LOCAL GAS UTILITY SHALL P-1 PUMP BELL & GOSSETT MODEL 11 FT(HEAD) @ 5 GPM. PUMP
<br /> TTO SINGLE PHASE 120 VOLT PUMP. 9 F pF CALG�O��o ISSUE DATE: 7-30-19
<br /> _ O BBE E LEAD FREE CONSTRUCTION.
<br /> INSTALL THEIR GAS SERVICE LINE TO THE GAS METER. TRENCHING SHALL BE IN ACCORDANCE WITH UTILITY STANDARDS. ALL CHARGES - - - - PROVIDE WITH AQS-3/4 AQUASTAT AND FLEXIBLE PLUG-IN CORD. REV. DATE: 12-20-1q
<br /> AND FEES INCURRED BY THE UTILITY FOR NEW GAS SERVICE SHALL BE PAID BY THE CONTRACTOR. INSTALL PER MANUFACTURERS INSTRUCTIONS.
<br /> 12. ALL DOMESTIC WATER PIPING SHALL BE A MINIMUM OF 1/2"SIZE UNLESS NOTED OTHERWISE. USE A REDUCING DROP ELL AT FIXTURE
<br /> LAW R E N C E PROJECT NO.: 18008.2
<br /> CONNECTION WHEN APPLICABLE. NOTES: ENGINEERING GROUP DRAWN BY: NL
<br /> A. SIZE MANUFACTURER'S RECOMMENDATION.
<br /> B. CLEANOUT SHALL BE SAME SIZE AS PIPE BEING SERVED. 7084 N.Maple Ave.,Suite 101 Fresno,CA 93720 SHEET:
<br /> P-2.2 - PLUMBING SCHEDULES AND SPECS C. THIS SCHEDULE IS COMPREHENSIVE. ALL MARKS MAYOR MAY NOT BE USED ON PLANS. (559) 431-0101 19368 FAX(559)431-1362
<br /> P-2 . 2