authorized,substances or components;soil or other !CAUTION
<br /> surface or subsurface conditions;or fire,flood,storm, Do not remove elastic band from around float until
<br /> lightning,earthquake,accident or any other conditions, instructed to do so,as damage to valve may result.
<br /> events or circumstances beyond OPW`s control.
<br /> WARNING
<br /> THIS I IMITED WARRANTY IS IN LIEU OF ALL OTHER Failure to properly connect delivery hose and el-
<br /> WARRANTIES,EXPRESS OR IMPLIED,AND ALL OTHER bow,and/or disconnecting a liquid filled delivery
<br /> WARRANTIES INCLUDING,WITHOUT LIMITATION,THE hose or elbow will result in a hazardous spill,which
<br /> WARRANTIES OF MERCHANTABILITY AND FITNESS FOR may result in personal injury,property damage,fire,
<br /> A PARTICULAR PURPOSE,ARE HEREBY EXCLUDED.. explosion,and water and soil pollution.
<br /> OPW shall have no other liability whatsoever,whether . Make sure all connections,including the hose and
<br /> based on breach of contract,negligence,gross negli- elbow connections,between storage tank and
<br /> gence,strict liability or any other clairn,including,with- transport are securely coupled.
<br /> out limitation,for special,incidental,consequential or
<br /> exemplary damages or for the cost of labor,freight,ex- • Make sure the lip seal and/or al!gaskets in the deliv-
<br /> cavation,clean-up,downtime,removal,reinstallation, ery elbow are properly in place to prevent spiifs.
<br /> loss of profit,or any other cost or charges.No person or a Do not operate with damaged or missing parts,
<br /> entity is authorized to assume on behalf of OPW any which prevent tight connections.
<br /> liability beyond this limited warranty.This limited war-
<br /> ranty is not assignable. Normal:Operation:A Hose'Kick" and reduced flow
<br /> signal that the tank is full, Close transport delivery
<br /> �*Date of manufacture on this product is located on valve and drain hose into tank before disconnecting
<br /> the flat area of the valve body,under float. any hose fitting.
<br /> Overfilled Tank:Failure of the hose to drain after
<br /> GENERAL INSTRUCTIONS closing the deliveryvalve signals an overfilled tank. Do
<br /> The OPW 7150 Overfill Prevention Valve is designed for Not Disconnect any delivery hose fitting until the liquid
<br /> tight fill,gravity drop applications to help prevent acci- level in the tank has been lowered to allow the hose to
<br /> dental or intentional overfilling of underground storage drain into the tank.
<br /> tanks. It is installed in the UST drop tube in place of a WARNING
<br /> standard drop tube. In the event you are splashed with fuel remove wet
<br /> The main 71 SO valve closes when liquid reaches the clothing immediately. Skin contact with gasoline
<br /> initial shut off point. A small bypass valve remalns open can cause chemical burns and may result in inhala-
<br /> to allow the delivery hose to drain at 3-5 gallons per tion of vapors that may be fatal. Never go inside
<br /> minute. If the delivery truck valve is not closed after confined areas after being splashed and never go
<br /> initial shut-off,the bypass valve will close and will re- near ignition sources.
<br /> strict all fuel deiivery to ensure that the top of the tank IMPORTANT
<br /> is not wetted per EPA requirements. Determine if the underground storage tank is equipped
<br /> The 7150 models of the 7150 are designed to be in- with a bail float vent valve,as illustrated in Figure 24. In
<br /> stalled with the following OPW products:Face Seal all systems,the shut-off point of the 7150 must be
<br /> Adaptor,OPW Spill Container or Multi-port,Jack Screw reached before the ball float reduces flow to ensure
<br /> Kit,Rotatable Product Adaptor,and Product Cap. proper overfill valve operation.
<br /> IMPMTANT TOOLS NEEDED FOR INSTALLATION AND ASSEM-
<br /> Read these assembly and installation instructions com- BLY:
<br /> pletely and carefully prior to starting. Check to make 1. 71 SO-TOOL or 71 SO-TOOLC or
<br /> sure all parts have been provided. Use only the parts
<br /> supplied;substitution of parts may cause product fail- 7150-TOOLCT(includes the following)
<br /> ure. + Sharp 3116"drill bit with stop
<br /> Failure to follow instructions may cause improper prod- ■ Punch
<br /> uct operation or premature failure which may permit NOTE: Testable 7150 models ending with a"T"re-
<br /> storage tank overfill. An overfilled storage tank may
<br /> create hazardous conditions and/or environmental con- quire the 7v TCrDerCT�r rvtllt3edt 30-TOOL or
<br /> tamination. 7'so-'r0QLC
<br /> 2
<br />
|