Laserfiche WebLink
PREVENTATIVE MAINTENANCE cations. Performance Requirement. Leak rate to be less <br /> Annually,inspect the flapper in the 7150 to see that it is than or equal to 0.17 CFH@2.W W.C. <br /> open by looking down the drop tube opening. Test the <br /> 7150 drop tube seals with CARB procedure TP-201.1 D. Torque Specification <br /> If the drop tube seal passes testing,no further mainte- Taptite Screws,#10-24 thread cutting,70 in-lbs mini- <br /> nance is required. If the drop tube fails testing,replace mum to 35 in-lbs maximum. Testable Models Only; <br /> the drop tube seal with OPW PIN:H11931 M for 4" Socket Adaptor, 114"NPT,3.5 ft-lbs X42 in-lbs}minimum <br /> Tubes. Re-test the 7150 drop tube with GARB proce- to 5.0 ft-lbs(60 in-lbs)maximum. <br /> lure TP-203.1 D. The lower tube o-ring seal OPW PIN: <br /> H14840M can also be replaced. 1f this does not correct IMPORTANT: Leave these installation instructions <br /> the leak the 7150 needs to be replaced. and maintenance procedures with the station opera- <br /> FOR TESTABLE MODELS ONLY: The socket adaptor tor. <br /> can be removed and poppet and float movement and <br /> function inspected without removing the valve. See <br /> Page 17 forfull testing details. If replacement parts are <br /> needed for testable models the following items are <br /> available: OPW PIN 206741 Testable Inlet Tube 51A, <br /> 206740 Socket Adaptor and Cable Assembly,and 61 SOK <br /> WQ01 Hoat Kit. <br /> CAUTION: Do not insert any foreign object into drop <br /> tune if flapper is in the closed position. For exam- <br /> ple,a tank level measuring stick. This will damage <br /> the valve and void the Warranty. ALWAYS check <br /> flapper location before"sticking"the tank. If flap- <br /> per is in the closed position,the tank is either over- <br /> filled and you need to wait until the liquid level goes <br /> down or the 71 SO Is damaged and needs to be re- <br /> place J. <br /> 7150 Performance Specifications <br /> This Overfill Prevention Valve has been manufactured <br /> and tested to,and met,the following California specifi- <br /> 18 <br />