Laserfiche WebLink
C Lor 9I1etals nal sis--TCLP <br /> Matrix-Spike/ Matrix S.jRike, Du Iicate/ LCS <br /> ANALYSIS DATE 6f1I2021 Unit:mg/L(ppm) <br /> Analysis Spk.Sample LCSLCS LCS Sample Spike MS % Rec MSD % Rec % RPD <br /> ID CONC. %Rec. STATUS Result Conc. MS MSD <br /> Cadrnium(Cd) 210527-2 1.00 102 PASS 0 1.00 0.862 86% 0.876 88%0 2% <br /> Chromium(Cr) 210527-2 1.00 99 PASS 0.058 1.00 0.927 87% 0.955 90/0 3% <br /> Lead(Pb) 210527-2 1.00105 PASS C} 1.00 0.964' 96% 0.953 96'% 1% <br /> ANALYSIS DATE. 5128/20211 <br /> Analysis Spk.SampleLCS LCS Sample Spike IVIS % Rec MSD % Rec % RPD <br /> ID CONC. %Rec. STATUS Result Conc. MS MSD <br /> Mercury(Hg) 210527-37 0.0125 95 PASS 0 0.0125 0.0109 87% 0.0112 90% 3% <br /> MSIMSD.Status. <br /> Analysis %MS %MSD %flLCS %RPD -' <br /> Cadmium(Cd) PASS PASS PASS PASS { <br /> Chromium(Cr)_ PASS PASS' PASS PASS ANALYST: <br /> Lead(Pb) PASS PASS PASS' PASS <br /> Mercury(Hg) PASS PASS PASS PASS, FINAL REVIEWER: <br /> Acce tad Range 75- 125 75-125 85-11-5 0-20 <br /> =Fail due to matrix interference <br /> Note:LCS is in control therefore results are in control <br />