Ross Robert Truck Repair Used Oil Tank <br /> Interim Assessment and Conditional Certification <br /> September 14, 2021 <br /> Optional: <br /> • The tank coating is worn off on in large areas of the tank top and sides and is not good condition. <br /> Spot painting uncoated areas will reduce corrosion on the tank. <br /> • The tank should have overfill protection, such as a tank level gauge that can be referenced by <br /> someone filling the tank. <br /> • General housekeeping should be improved by removing any rags from the tank top and cleaning <br /> up absorbents on the floor. <br /> The estimated remaining service life of this tank system could be 5 to 10 plus years. The next Title 22 <br /> certification for this tank is due in five years, July 20, 2026. <br /> Based on the integrity testing results, reported in Section 6.0 of this report, the tank has sufficient <br /> integrity for its intended use once the following is corrected: venting, the tank is anchored and has a <br /> NFPA sticker and Hazardous Waste Accumulation sticker added to the tank. This Interim Report will <br /> be updated and stamped at that time. <br /> The tank system has been inspected for the presence of any of the following items: <br /> (1)weld breaks; <br /> (2)punctures; <br /> (3) scrapes of protective coatings; <br /> (4) cracks; <br /> (5) corrosion; <br /> (6) other structural damage or inadequate construction or installation. <br /> The tank was found to have none of the following: Weld breaks, punctures, cracks or other structural <br /> damage. Scrapes and removal of portions of the protective coating do not appear to affect the integrity <br /> of the tank. <br /> 8.0 References <br /> • CCR Title 22 <br /> • Steel Tank Institute, Standard for the Inspection of Aboveground <br /> Storage Tanks SP-001 <br /> • NFPA 30 <br /> • Standard Hand Book for Mechanical Engineers <br /> • International Building Code <br /> 8 <br />