Laserfiche WebLink
Closed <br />Figure 29 <br />INSP 6. If there is no apparent damage or restrictions <br />reinstall the valve per the above instructions and test <br />per local requirements. <br />71 SO Performance Specifications <br />This Overfill Prevention Valve has been manufactured <br />and tested to, and met, the following California specifi- <br />cations. Performance Requirement: Leak rate to be less <br />than or equal to 0.17 CFH@2.0" W.C. <br />Torque Specification <br />Taptite Screws, #10-24 thread cutting, 20 in-lbsmini- <br />mum to 35 indbs maximum. Testable Models Only: <br />Socket Adaptor, 1/4" NPT, 3.5 ft -lbs (42 indbs) minimum <br />to 5.0 ft -lbs (60 indbs) maximum. <br />IMPORTANT: Leave these installation instructions <br />and maintenance procedures with the station opera- <br />tor. <br />MAR 1 z 2019 <br />ENV1RnNM�NTAL HEALTH <br />DEPARTMENT <br />19 <br />